国产强伦姧在线观看无码,中文字幕99久久亚洲精品,国产精品乱码在线观看,色桃花亚洲天堂视频久久,日韩精品无码观看视频免费

      產(chǎn)品|公司|采購|資訊

      MRU-21系列接地電阻和電導(dǎo)測(cè)試儀

      參考價(jià)面議
      具體成交價(jià)以合同協(xié)議為準(zhǔn)
      • 公司名稱康寶萊儀表(珠海)有限公司
      • 品       牌
      • 型       號(hào)
      • 所  在  地
      • 廠商性質(zhì)
      • 更新時(shí)間2018/5/14 9:00:00
      • 訪問次數(shù)670
      產(chǎn)品標(biāo)簽:

      在線詢價(jià)收藏產(chǎn)品 點(diǎn)擊查看電話

      聯(lián)系我們時(shí)請(qǐng)說明是 智能制造網(wǎng) 上看到的信息,謝謝!

      Index: WMGBMRU21 Possible measurements: earth resistance measurment with 3-pole method, measurement of continuity of equipotential bondings and protective conductors with auto-zero function - with cur
      MRU-21系列接地電阻和電導(dǎo)測(cè)試儀 產(chǎn)品信息

      Possible measurements:

      • earth resistance measurment with 3-pole method,
      • measurement of continuity of equipotential bondings and protective conductors with auto-zero function - with current 200mA,
      • resistance measurement using 2-pole method.

      MRU-120 Technical Specifications
       

      It allows to take the measurements of:

      • earthing resistance using auxiliary electrodes,
      • earthing resistance using auxiliary electrodes and clamp (for measurements of multiple earthing)
      • earthing resistance using double clamps (for measurement of earthing when it is impossible to use auxiliary electrodes),
      • ground resistivity (Wenner method),
      • measurement of continuity of equipotential bondings and protective conductors (meeting the requirements of IEC 60364-6-61:2000 section 6.12.2) with auto-zero function – with current 200mA.
         

      Additionally:

      • measurement of resistance of auxiliary electrodes RS and RH,
      • measurement of interference voltage,
      • measurement of interference frequency,
      • measurement in the presence of interference voltage in the power network with frequency 50Hz, 60Hz
      • selection of maximum measuring voltage (25V and 50V)
      • introducing the distance between the electrodes for the resistivity in metres (m),
      • memory of 990 measurements (10 banks of 99 cells each),
      • calibration of clamp used,
      • real time clock (RTC),
      • data transmission to the computer (USB, wireless),
      • indication of battery state.
      Electric security:
      - type of insulation: double, according to  EN 61010-1 and IEC 61557
      - measurement category: CAT IV 300V acc. to EN 61010-1
      - protection class acc. to EN 60529: IP54

      Rated operational conditions:

      - operation temperature: -10...+50°C
      - storage temperature: -20...+70°C
      - humidity: 20...80%

      Other technical data:

      - LCD display: graphic, backlighted
      - interface: USB, wireless
      - number of measurements carried out of set of batteries: > 500
      - warranty: 36 months

       

      Measurement of interference voltage

      Range Resolution Accuracy
      0...100V 1V ±(2% m.v + 3 digits)

      • singnalling  overvoltage 24V or 40V rms
      • measurement for DC and AC 45…65 Hz,


      Measurement of earthing resistance (method 3- and 4-pole)

      measurement range to IEC61557-5: 0,30Ω...19,9kΩ

      Range Resolution Accuracy
      0,00...19,99Ω 0,01Ω
      ±(2% m.v. + 2 digits)
      20,0...199,9Ω 0,1Ω
      200...1999Ω
      2,0k...9,99kΩ 0,01kΩ  ±(5% m.v. + 4 digits)
      10,0k...19,9kΩ 0,1kΩ

      • measurement current: under short circuit >200mA,
      • voltage on open terminals: selectable <25V AC or <50V AC,
      • frequency of measurement current: 125 (for networks 50Hz) or 150Hz (for 60Hz),
       
      Measurement of continuity of equipotential bondings and protective conductors (Rcont)
      measurement range to IEC61557-5: 0,24Ω...19,9kΩ
       

      Range Resolution Accuracy
      0,00...19,99Ω 0,01Ω
      ±(2%  m.v. + 2 digits)
      20,0...199,9Ω 0,1Ω
      200...1999Ω
      2,0k...9,99kΩ 0,01kΩ  ±(5%  m.v. + 2 digits)
      10,0k...19,9kΩ 0,1kΩ

      •voltage on open terminals: <24Vrms but >4Vrms,
      • measurement current: under short circuit >200mA,
      • frequency of measurement current: 125 (for networks 50Hz)  
        or 150Hz (for networks 60Hz), possible choice of measurement frequency in menu,
      • auto-zero function measurement leads

      Measurement of resistance of auxiliary electrodes RH and RS
       

      Range Resolution Accuracy
      0...999Ω
      ±(5% (RS+RE+RH) + 8 digits)
      1,00k...9,99kΩ 0,01kΩ
      10,0k...19,9kΩ 0,1kΩ


      Measurement of multiple earthing resistance with using the clamp and auxiliary electrodes (3p + clamp)

      measurement range to IEC61557-5: 0,44Ω...1999Ω

      Range Resolution Accuracy
      0,00...19,99Ω 0,01Ω
      ±(8% m.v. + 3 cyfry)
      20,0...199,9Ω 0,1Ω
      200...1999Ω

      • voltage on open terminals: selectable <25V AC or <50V AC,
      • measurement current: under short circuit > 200mA,
      • frequency of measurement current: 125 (for networks 50Hz)
        or 150Hz (for 60Hz),


      Measurement of multiple earthing resistance with using double clamps

      Range Resolution Accuracy
      0,00..19,99Ω 0,01Ω ±(10% m.v. + 3 digits)
      20,0...149,9Ω 0,1Ω ±(20% m.v. + 3 digits)

      • frequency of measurement current 125 (for networks 50Hz)
        or 150Hz (for networks 60Hz)


      Measurement of ground resistivity
      Measurement method: Wennera, ρ=2πLRE
       

      Range Resolution Accuracy
      0,0...199,9Ωm 0,1Ωm depending on measurement
      accuracy RE with 4p method,
      but not less than ±1 digit
      200...1999Ωm 1Ωm
      2,00k...19,99kΩm 0,01kΩm
      20,0k...99,9kΩm 0,1kΩm
      100k...999kΩm 1kΩm

      L – distance between probes: 1...50m
      在找 MRU-21系列接地電阻和電導(dǎo)測(cè)試儀 產(chǎn)品的人還在看