SCONI-AR-DC信號(hào)避雷器SIGNAL ARRESTER
Order information
SCONI – AR – DC
General specification
Mounting drawing
Item Specification
Max Line
Voltage 30V
Discharge
Voltage
L to L : More than 30V
L to G : Less than 500V
Max Surge
Voltage 40V
Internal
Series Res Approx 20Ω
Discharge
Current 1000A(8 x 20 ㎲)
Max Load
Current 100mA
Response
time Less than 0.1 ㎲
L to L Leakage : Less than 5㎂(30V DC)
Current L to G : Less than 5㎂(140V DC)
Operating
Temperature -5 ~ 55℃
Operating
Humidity 10 ~ 90% RH(non-condensing)
Rail Type : W 23 x H 79 x D 83 mm
Dimension
Panel Type : W 23 x H 80 x D 80 mm
General
This model is used to 2 wire signal transmitter.
It absorbs the lightning surge which is induced in
signal line. Then it keeps low line voltage for
prevent electronic component’s damage from
lightning surge.
It discharges lightning surge into ground and
connection of signal lines are restored
automatically after definite time.
S
S
+ P
P
G
GROUND TERMINAL
BASE
ASSEMBLY
ELEMENT
ASSEMBLY
DISCHARGE
ELEMENT