橫河UT75A-004-10-00數(shù)字指示調(diào)節(jié)器UT75A-004-10-00溫控表
Types of input | Instrument range | Accuracy | ||
°C | °F | |||
Thermocouple | K | -270.0 to 1370.0°C | -450.0 to 2500.0°F | ±0.1% of instrument range ±1 digit for 0°C or more ±0.2% of instrument range ±1 digit for less than 0°C However, ±2% of instrument range ±1 digit for less than -200°C of thermocouple K ±1% of instrument range ±1 digit for less than -200°C of thermo- couple T |
-270.0 to 1000.0°C | -450.0 to 2300.0°F | |||
-200.0 to 500.0°C | -200.0 to 1000.0°F | |||
J | -200.0 to 1200.0°C | -300.0 to 2300.0°F | ||
T | -270.0 to 400.0°C | -450.0 to 750.0°F | ||
0.0 to 400.0°C | -200.0 to 750.0°F | |||
B | 0.0 to 1800.0°C | 32 to 3300°F | ±0.15% of instrument range ±1 digit for 400°C or more ±5% of instrument range ±1 digit for less than 400°C | |
S | 0.0 to 1700.0°C | 32 to 3100°F | ±0.15% of instrument range ±1 digit | |
R | 0.0 to 1700.0°C | 32 to 3100°F | ||
N | -200.0 to 1300.0°C | -300.0 to 2400.0°F | ±0.1% of instrument range ±1 digit ±0.25% of instrument range ±1 digit for less than 0°C | |
E | -270.0 to 1000.0°C | -450.0 to 1800.0°F | ±0.1% of instrument range ±1 digit for 0°C or more ±0.2% of instrument range ±1 digit for less than 0°C However, ±1.5% of instrument range ±1 digit for less than -200.0°C of thermocouple E | |
L | -200.0 to 900.0°C | -300.0 to 1600.0°F | ||
U | -200.0 to 400.0°C | -300.0 to 750.0°F | ||
0.0 to 400.0°C | -200.0 to 1000.0°F | |||
W (*2) | 0.0 to 2300.0°C | 32 to 4200°F | ±0.2% of instrument range ±1 digit | |
Platinel 2 | 0.0 to 1390.0°C | 32.0 to 2500.0°F | ±0.1% of instrument range ±1 digit | |
PR20-40 | 0.0 to 1900.0°C | 32 to 3400°F | ±0.5% of instrument range ±1 digit for 800°C or more Accuracy not guaran- teed for less than 800°C | |
W97 Re3-W75 Re25 | 0.0 to 2000.0°C | 32 to 3600°F | ±0.2% of instrument range ±1 digit | |
Resistance-temperature | JPt100 | -200.0 to 500.0°C | -300.0 to 1000.0°F | ±0.1% of instrument range ±1 digit (*1) |
-150.00 to 150.00°C | -200.0 to 300.0°F | ±0.1% of instrument range ±1 digit | ||
Pt100 | -200.0 to 850.0°C | -300.0 to 1560.0°F | ±0.1% of instrument range ±1 digit (*1) | |
-200.0 to 500.0°C | -300.0 to 1000.0°F | |||
-150.00 to 150.00°C | -200.0 to 300.0°F | ±0.1% of instrument range ±1 digit | ||
Standard signal | 0.400 to 2.0000 V | - | ±0.1% of instrument range ±1 digit | |
1.000 to 5.000 V | - | |||
4.00 to 20.00 mA | - | |||
DC voltage | 0.000 to 2.000 V | - | ||
0.00 to 10.00 V | - | |||
-10.00 to 20.00 mV | - | |||
0.0 to 100.0 mV | ||||
DC current | 0.00 to 20.00 mA | - |
Model | Suffix code | Optional suffix code | Description | |||||
UT75A | | | | | | | | Digital Indicating Controller (provided with retransmission output or 15 V DC loop power supply , 3 DIs,and 3 DOs) (Power supply 100-240 V AC) |
Type 1: Basic con- trol (*1) | -0 | | Standard type | |||||
-1 | | Position proportional type | ||||||
-5 | | Dual-loop type | ||||||
Type 2: Functions (*1) | 0 | | 5 additional DIs and 5 additional DOs | |||||
1 | | Remote (1 additional aux. analog) input, RS485 communication (Max.19.2 kbps, 2-wire), 1 additional DI,and 5 additional Dos | ||||||
2 | | Remote (2 additional aux. analog) inputs, RS485 communication (Max.19.2 kbps, 2-wire), 2 additional DIs | ||||||
Type 3:Open networks | 0 | | None | |||||
1 | | RS-485 communication (Max.38.4 kbps, 2-wire/4-wire) and 5 additional DIs | ||||||
2 | | Ethernet communication (with serial gateway function) | ||||||
3 | | CC-Link communication (with Modbus master function) | ||||||
4 | | PROFIBUS-DP communication (with Modbus master function) | ||||||
5 | | DeviceNet communication (with Modbus master function) | ||||||
Display language (*2) | -1 | | English | |||||
-2 | | German | ||||||
-3 | | French | ||||||
-4 | | Spanish | ||||||
Case color | 0 | | White (Light gray) | |||||
1 | | Black (Light charcoal gray) | ||||||
Fixed code | -00 | | Always “-00” | |||||
Options | /DC | Power supply 24 V AC/DC | ||||||
/CT | Coating (without safety standard (UL/CSA) and CE markings) | |||||||
/CP | Carbon potential calculation function (*3) |
*2: English, German, French, and Spanish can be displayed as the guide display.
*3: When Type 2 code is “1” or “2”, the /CP option can be specified.