      2604/2704 碳勢控制表功能說明

      2604/2704 碳勢控制表功能說明

       

      Carburising

      When Mild steels or certain low carbon steels are heated at temperatures above 900oC in a carbon rich atmosphere, the surface of the steel absorbs carbon by diffusion. The depth of carbon enrichment depends on the time and temperature of the treatment known as carburising. The presence of carbon in the steel causes a change in its physical properties. Accurate control of both temperature and carbon potential are needed to achieve the required profile of carbon enrichment.

      Zirconia Sensor Theory

      The Zirconia probe generates a millivolt signal based on the ratio of oxygen concentration between the reference airside of the probe (outside the furnace) and the amount of oxygen actually inside the furnace. Temperature is measured using a built in thermocouple at the tip of the probe. Together, these signals are used by the 2604 zirconia function block to calculate the actual percentage of carbon in the furnace atmosphere. The 2604 oxygen probe interface is compatible with most commonly used zirconia probes.

       

      2604 Integrated Furnace Controller

                    Synchronised temperature/carbon profiles

                    Automatic probe cleaning

                    Furnace sooting alarm

                    Probe deterioration alarm

                    Temperature control of quench

       

       

       

       

       

       

       

       

       

       

       

      A 2604 three loop controller is used to control both furnace temperature, carbon potential and quench. In many batch furnace applications a setpoint programmer is used to generate temperature and carbon profiles which are synchronised to a common time base.

      Furnace Temperature Control

      Although the sensor input of the temperature loop can come from the zirconia probe, it is more common for a separate thermocouple to be used. The heat control output can either be connected to gas burners or thyristors. In some applications a cooling output may also be connected to a circulation fan or an exhaust damper.

      Furnace Atmosphere control

      In atmosphere loops the controller increases the carbon potential by opening a solenoid valve which allows a carburising gas (ie propane) to enter the furnace. Conversely, to decrease the carbon potential, air or nitrogen is introduced into the furnace. Automatic probe cleaning functions ensure that the reading is accurate, whilst probe health and sooting alarms warn of a deterioration in the probes performance.

      Quench Temperature Control

      Steel parts are rapidly cooled (Quenched) from around 850oC to obtain the desired hardness, strength or toughness. Depending on the material being treated, the quench medium is usually oil or water. The quench control loop maintains the quench bath at the desired temperature and provides a quench timer facility.

      Sooting Alarm

      As well as alarms on the temperature and carbon potential in the furnace the 2604 can trigger an alarm, when the atmospheric conditions are such that carbon will be deposited as soot on all surfaces inside the furnace, including the workpiece. Avoiding sooting protects the furnace lining, maintains the accuracy of the zirconia probe and stops formation of a soot barrier on the workpiece which can prevent carbon diffusion.

      Automatic Probe Cleaning

      The 2604 has a probe clean and recovery strategy that can be programmed to occur between batches or manually requested by an operator. A short blast of compressed air is used to remove any soot and other particles that may have accumulated on the probe. Once the cleaning has been completed the time taken for the probe to recover is measured. If the recovery time is too long this indicates that the probe is ageing and replacement or refurbishment is due. During the cleaning and recovery cycle, the %CP reading is frozen thereby ensuring continuous furnace operation.

      Enriching Gas Correction

      A gas analyser can be used to determine the CO concentration of the enriching gas. If an analogue output is available from the analyser, it can be fed into the 2604 to automatically adjust the calculated % carbon reading. Alternatively, an operator may enter this value manually.

       

      英國歐陸碳勢控制儀2404/2408

      2400系列是帶有自整定功能及自適應(yīng)功能的PID高精度溫度控制器。

      歐陸EUROTHERM碳勢控制儀2604/2704

      $r$n$r$n2604/2704 碳勢控制表功能說明$r$n $r

      歐陸EUROTHERM碳勢控制儀3504

      3500系列可編程控制器適用于精確的溫度,碳勢,露點,氧勢控制。350

      會員登錄

      ×

      請輸入賬號

      請輸入密碼

      =

      請輸驗證碼

      收藏該商鋪

      X
      該信息已收藏!
      標(biāo)簽:
      保存成功

      (空格分隔,最多3個,單個標(biāo)簽最多10個字符)

      常用:

      提示

      X
      您的留言已提交成功!我們將在第一時間回復(fù)您~

      以上信息由企業(yè)自行提供,信息內(nèi)容的真實性、準(zhǔn)確性和合法性由相關(guān)企業(yè)負(fù)責(zé),智能制造網(wǎng)對此不承擔(dān)任何保證責(zé)任。

      溫馨提示:為規(guī)避購買風(fēng)險,建議您在購買產(chǎn)品前務(wù)必確認(rèn)供應(yīng)商資質(zhì)及產(chǎn)品質(zhì)量。

      在線留言