上海倍加福工業(yè)自動(dòng)化貿(mào)易有限公司
您現(xiàn)在的位置: 上海倍加福工業(yè)自動(dòng)化貿(mào)易有限公司>>工業(yè)電源>> PS1000-D2-24.20.RM
PS1000-D2-24.20.RM
參考價(jià): | 面議 |
- 產(chǎn)品型號(hào)
- 品牌
- 其他 廠商性質(zhì)
- 所在地
訪問次數(shù):103更新時(shí)間:2023-10-06 19:39:11
聯(lián)系我們時(shí)請(qǐng)說明是智能制造網(wǎng)上看到的信息,謝謝!
產(chǎn)品介紹
技術(shù)參數(shù)節(jié)選 PS1000-D2-24.20.RM
Electrical specifications | ||
---|---|---|
Voltage drop | input to output 0.1 ... 0.5 V at input 2 x 5 A 0.2 ... 0.5 V at input 2 x 10 A 0.24 ... 0.5 V at input 2 x 12 A load share dependent | |
Power dissipation | 1.7 W no load 2.6 ... 4.7 W at input 2 x 5 A 5.6 ... 8.7 W at input 2 x 10 A | |
Input | ||
Rated voltage | 24 ... 28 V | |
Voltage range | 18 ... 35 V DC | |
Current | 2 x 12 A at ambient temperature < 45="" °c="" (113="" °f)=""> 2 x 10 A at ambient temperature 70 °C (158 °F) 2x 17 mA for max. 5 s for lower output currents see technical information | |
Output | ||
Voltage range | 24 ... 28 V DC | |
Current | 24 A at ambient temperature < 45="" °c="" (113="" °f)=""> 20 A at ambient temperature < 70="" °c="" (158="" °f)=""> 32.5 A for max. 5 s max. 26 A in overload or short circuit mode (voltage < 6="" v=""> | |
Fault indication output | ||
Connection | terminals 13, 14 : relay contact load share terminals 23, 24 : relay contact redundancy | |
Output type | relay contact load share - contact is closed if the adjustment of the output voltages are sufficient - contact is open if an even load share does not occur and readjustment of the output voltage is required relay contact redundancy - contact is closed if no fault is detected - contact is open if one or both input voltages are below 22 V DC or above 30 V DC - contact is open if the output current is higher than the adjusted value of the output current - contact is open if an internal defect of the device is detected | |
Contact loading | max. 60 V DC/0.3 A ; 30 V DC/1 A ; 30 V AC/0.5 A resistive load min. 1 mA at 5 V DC | |
Galvanic isolation | ||
Input/Output | SELV/PELV | |
Indicators/settings | ||
Display elements | LED green: output status - LED lights up if the output current is smaller than the adjusted value of the output current LEDs green: load share status - LEDs indicate the load share status between the two power supplies LED green: redundancy status - LED lights up if no fault is detected - LED flashes if one ore both input values are below 22 V or above 30 V - LED flashes if the output current is higher than the adjusted value of the output current - LED flashes if an internal defect is detected | |
Control elements | rotary switch | |
Configuration | setting of the output current via rotary switch - switch setting to 5 A in combination with two 5A power supplies (1+1 redundancy) - switch setting to 10 A in combination with two 10A power supplies (1+1 redundancy) - switch setting to 20 A for N+1 redundant systems | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | IEC/EN 61000-6-1 , IEC/EN 61000-6-2 , IEC/EN 61000-6-3 , IEC/EN 61000-6-4 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1 | |
RoHS | ||
Directive 2011/65/EU (RoHS) | IEC/EN 63000:2019 | |
Conformity | ||
Degree of protection | EN 60529 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) , see technical information | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | 5 ... 95 %, noncondensing | |
Shock resistance | 20 g , 11 ms or 30 g , 6 ms | |
Vibration resistance | 2 ... 17.8 Hz : ± 1.6 mm , 17.8 ... 500 Hz : 2 g | |
Mechanical specifications | ||
Housing material | aluminum alloy , galvanized steel | |
Degree of protection | IP20 | |
Connection | ||
Input/Output | screw terminals conductor cross section: max. 6 mm2 (AWG 20-10) cable diameter: max. 2.8 mm, wire end ferrules included stripped insulation length: 7 mm tightening torque: max. 0.8 Nm | |
Relay contact output | spring terminals conductor cross section: max. 1.5 mm2 (AWG 24-16) cable diameter: max. 1.6 mm, wire end ferrules included stripped insulation length: 7 mm | |
Mass | approx. 310 g | |
Dimensions | 32 x 124 x 117 mm (W x H x D) , without DIN mounting rail | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
ATEX approval | ||
ATEX certificate | EPS 11 ATEX 1 312 X | |
ATEX marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2016 , EN 60079-15:2010 | |
International approvals | ||
UL approval | E223176 | |
IECEx approval | ||
IECEx certificate | IECEx EPS 20.0057X | |
IECEx marking | Ex ec nC IIC T4 Gc | |
Standards | IEC 60079-0:2011 , IEC 60079-7:2015 , IEC 60079-15:2010 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see . |
Classifications
System | Classcode |
---|---|
ECLASS 13.0 | |
ECLASS 12.0 | |
ECLASS 11.0 | |
ECLASS 10.0.1 | |
ECLASS 9.0 | |
ECLASS 8.0 | |
ECLASS 5.1 | |
ETIM 9.0 | EC002542 |
ETIM 8.0 | EC002542 |
ETIM 7.0 | EC002542 |
ETIM 6.0 | EC002542 |
ETIM 5.0 | EC002542 |
UNSPSC 12.1 |