SINAMICS G120 standard inverters跳轉(zhuǎn)到概述 優(yōu)勢(shì) 設(shè)計(jì) 組態(tài) 技術(shù)規(guī)范 概述The SINAMICS G120 frequency inverter is designed to provide precise and cost-effective speed/torque control of three-phase motors. With different device versions (frame sizes FSA to FSGX) in a power range from 0.37 kW to 250 kW (0.5 hp to 400 hp), it is suitable for a wide variety of drive solutions.  Example: SINAMICS G120, frame sizes FSA, FSB and FSC; each with Power Module, CU240E?2 F Control Unit and Basic Operator Panel BOP-2  Example: SINAMICS G120, frame sizes FSD, FSE and FSF; each with Power Module, CU240E?2 F Control Unit and Inligent Operator Panel IOP  Example: SINAMICS G120, frame size FSGX; with Power Module, CU240E?2 F Control Unit and Basic Operator Panel BOP-2 Operator-friendly design SINAMICS G120 is a modular inverter system that essentially comprises two function units: - Control Unit (CU)
- Power Module (PM)
The Control Unit controls and monitors the Power Module and the connected motor using several different closed-loop control types that can be selected. It supports communication with a local or central controller and monitoring devices. The Power Module supplies the motor in the power range 0.37 kW to 250 kW (0.5 hp to 400 hp). It features state-of-the-art IGBT technology with pulse-width-modulated motor voltage and selectable pulse frequency. Comprehensive protection functions provide a high degree of protection for the Power Module and the motor. The Control Units can be combined with the following Power Modules: Control Units | Power Modules degree of protection IP20 |
---|
| PM240?2 | PM240 | PM250 |
---|
CU230P?2 | ? | ? | ? | CU240E?2 | ? | ? | ? | CU250S?2 | ? | ? | ? | Safety Integrated SINAMICS G120 standard inverters are available in different versions for safety-related applications. The PM240?2 and PM250 Power Modules are already designed for Safety Integrated. PM240 Power Modules, frame size FSGX (i.e. 160 kW/250 hp and higher) are approved only for the Basic Safety functions (STO, SS1, and SBC). A drive can be combined with a Control Unit with safety functions (see overview) in order to create a Safety Integrated drive. The availability of Safety Integrated functions depends on the type of Control Unit. Control Unit | Basic Safety functions | Extended Safety functions |
---|
| STO | SS1 | SBC 1) | SLS | SDI | SSM |
---|
CU230P?2 | – | – | – | – | – | – | CU240E?2 | ? | – | – | – | – | – | CU240E?2 F | ? | ? | – | ? | ? | ? 2) | CU250S?2 | ? | ? | ? | ? 3) | ? 3) | ? 3) | 1) The SBC function can be utilized only if a Safe Brake Relay is installed. 2) SSM possible only for CU240E?2 DP?F / CU240E?2 PN?F Control Units with PROFIsafe. 3) With license for Extended Safety functions. Basic Safety functions (certified according to IEC 61508 SIL 2, and EN ISO 13849?1 PL d and Category 3) - Safe Torque Off (STO)
to protect against active movement of the drive - The PM240?2 Power Modules, frame sizes FSD to FSF additionally offer STO acc. to IEC 61508 SIL 3 and EN ISO 13489?1 PL e and Category 3.
- Safe Stop 1 (SS1)
for continuous monitoring of a safe braking ramp - Safe Brake Control (SBC) is used to safely control a holding
brake. When enabled, SBC is always activated at the same time as STO. The Safe Brake Relay is used for SBC.
Extended Safety functions (certified according to IEC 61508 SIL 2 and EN ISO 13849?1 PL d and Category 3) - Safely Limited Speed (SLS)
for protection against dangerous movements on exceeding a speed limit - Safe Direction (SDI)
This function ensures that the drive can only rotate in the selected direction. - Safe Speed Monitoring (SSM)
This function signals if a drive operates below a specific speed/feed velocity.
Basic Safety and Extended Safety functions can be activated via PROFIsafe or by means of the safety inputs. None of the safety functions require a motor encoder and they are thus cheaper and easier to implement. Existing systems in particular can be simply updated with safety technology without the need to change the motor or mechanical system. The Safe Torque Off (STO) function can be used without restriction for all applications. The SS1, SLS, SSM and SDI functions are only permissible for applications where the load can never accelerate when the inverter is switched off. They are therefore not permitted for applications involving pull-through loads such as hoisting gear and unwinders. Additional information is provided in chapter Highlights, section Safety Integrated. Efficient Infeed Technology The innovative Efficient Infeed Technology is employed in PM250 Power Modules. This technology allows the energy produced by motors operating in generator mode connected to standard inverters to be fed back into the supply system. For control cabinets, an additional temperature rise can be avoided and the amount of space required can be reduced due to the fact that components such as braking resistors, braking choppers and line reactors can be eliminated. Further, wiring and engineering costs are significantly reduced. At the same time, energy consumption can be reduced and ongoing operating costs noticeably reduced. Additional information is provided in chapter Highlights, section Efficient Infeed Technology. Innovative cooling concept and varnishing of electronic modules The new cooling system and varnishing of the electronic modules significantly increases the service life or useful life of the device. - Disposal of all heat losses via an external heat sink
- Consequential convection cooling of the Control Unit, electronic modules are not located in the air duct
- All cooling air from the fan is directed through the heat sink
Energy efficiency Integrated technologies help when optimizing the energy usage of the plant or system referred to the particular application: - Energy-efficient vector control with or without sensors
- Automatic flux reduction with U/f ECO mode
- Integrated energy saving computer
Additional information is provided in chapter Highlights, section Energy efficiency. 
優(yōu)勢(shì)- Modularity ensures flexibility for a drive concept that is fit for the future
- Control Unit can be hot-swapped
- Pluggable terminals
- The modules can be easily replaced, which makes the system extremely service friendly
- The integrated safety functions significantly reduce the costs when integrating drives into safety-oriented machines or systems
- Communications-capable via PROFINET or PROFIBUS with PROFIdrive Profile 4.0
- Plant-wide engineering
- Easy to handle
- The innovative circuit design (bidirectional input rectifier with "pared-down" DC link) allows the kinetic energy of a load to be fed back into the supply system when PM250 Power Modules are used. This feedback capability provides enormous potential for savings because generated energy no longer has to be converted into heat in a braking resistor
- Integrated USB interface for simplified, local commissioning and diagnostics
- Application-specific functions for pumps, fans and compressors
Integrated are, e.g.:- 4 freely-programmable PID controllers
- Application-specific wizards
- Pt1000/LG-Ni1000 temperature sensor interface
- 230 V AC relay
- 3 freely-programmable digital time switches
- With CU250S?2 Control Units: Integrated positioning functionality (basic positioner EPos) supports process-related implementation of positioning tasks with a high dynamic response. Positioning can be implemented with an incremental and/or absolute encoder (SSI)
- With CU250S?2 Control Units: Encoder interfaces DRIVE?CLiQ, HTL/TTL/SSI (SUB?D) and resolver/HTL (terminal)
- With CU250S?2 Control Units: Vector control with or without sensors
- Integrated control functionality by using BICO technology
- An innovative cooling concept and coated electronic modules increase robustness and service life
- External heat sink
- Electronic components are not located in air duct
- Control Unit that is compley cooled by convection
- Additional coating of the most important components
- Simple unit replacement and quick copying of parameters using an optional Operator Panel or an optional memory card
- Quiet motor operation as a result of the high pulse frequency
- Compact, space-saving design
- Software parameters for simple adaptation to 50 Hz or 60 Hz motors (IEC or NEMA motors)
- 2/3-wire control for static/pulsed signals for universal control via digital inputs
- Fast engineering and commissioning by using standard engineering tools such as SIZER for Siemens Drives, STARTER, SINAMICS Startdrive, and Drive ES – STARTER is integrated into STEP 7 using Drive ES Basic, with all of the benefits of central data management and totally integrated communication
- Certified worldwide for compliance with CE, UL, cUL, C-Tick (RCM) and Safety Integrated according to IEC 61508 SIL 2 and EN ISO 13849?1 PL d and Category 3
- The PM240?2 Power Modules, frame sizes FSD to FSF additionally offer STO acc. to IEC 61508 SIL 3 and EN ISO 13489?1 PL e and Category 3.

設(shè)計(jì)Application-orientated design of SINAMICS G120 SINAMICS G120 standard inverters are modular inverters for standard drives. Selection of the SINAMICS G120 is reduced to two or three steps thanks to the modular system used.  Selecting the Control Unit The optimum Control Unit is selected first, based on the number of I/Os and any additional functions required such as Safety Integrated or HVAC. The communication options are already integrated and do not have to be additionally ordered or plugged in. Three product series are available corresponding to the particular application. CU230P?2 Control Units The CU230P?2 Control Units have been specifically designed for pump, fan and compressor applications. The CU230P?2 is the Control Unit for the pump, fan and compressor inverters SINAMICS G120P and SINAMICS G120P Cabinet. Detailed information can be found in Catalog D 35. Control Unit CU240E?2 The CU240E?2 Control Unit is suitable for a wide range of applications in general machine construction, such as conveyor belts, mixers and extruders. CU250S?2 Control Units The CU250S?2 Control Units are suitable for applications involving single drives with exacting speed control requirements such as extruders and centrifuges, and for positioning tasks such as conveyor belts, lifting/lowering devices, etc. They can also be used to implement multi-motor drives without DC coupling such as wire-drawing machines and simple material lines.  Description | Fieldbus | Profile | Inputs Outputs | Integrated safety technology | Fail-safe digital inputs digital outputs | Control Unit |
---|
| | | | | | Article No. |
---|
CU230P?2 series - the specialist for pumps, fans, compressors, water, buildings Technology functions (selection): Free function blocks (FFB), 4 × PID controller, cascade connection, hibernation mode, essential service mode, multi-zone control | CU230P?2 HVAC | - USS
- Modbus RTU
- BACnet MS/TP
- FLN P1
| – | 6 DI 4 AI 3 DO 2 AO | – | – | 6SL3243-0BB30-1HA3 | CU230P?2 DP | | | 6SL3243-0BB30-1PA3 | CU230P?2 PN | | | 6SL3243-0BB30-1FA0 | - ODVA AC drive
- SINAMICS profile
| – | CU240E?2 series – for standard applications in general machinery construction, such as conveyor belts, mixers and extruders – without encoder Technology functions (selection): Free function blocks (FFB), 1 × PID controller, motor holding brake | CU240E?2 | | – | 6 DI 2 AI 3 DO 2 AO | STO | 1 F-DI (opt. for each 2 DI) | 6SL3244-0BB12-1BA1 | CU240E?2 DP | | | 6SL3244-0BB12-1PA1 | CU240E?2 PN | | - PROFIdrive
- PROFIsafe
- PROFIenergy
| 6SL3244-0BB12-1FA0 | - ODVA AC drive
- SINAMICS profile
| – | CU240E?2 F | | – | STO, SS1, SLS, SDI | 3 F-DI (opt. for each 2 DI) | 6SL3244-0BB13-1BA1 | CU240E?2 DP?F | | | STO, SS1, SLS, SSM 1), SDI | 6SL3244-0BB13-1PA1 | CU240E?2 PN?F | | - PROFIdrive
- PROFIsafe
- PROFIenergy
| 6SL3244-0BB13-1FA0 | - ODVA AC drive
- SINAMICS profile
| – | CU250S?2 series – for complex applications such as extruders and centrifuges – with and without encoder (basic positioner (EPos) optional) Technology functions (selection): Free function blocks (FFB), 1 × PID controller, motor holding brake | CU250S?2 | | – | 11 DI 2 AI 3 DO 2 AO 4 DI/DO (DI can be used as high-speed inputs) | STO, SBC, SS1 | 3 F-DI (opt. for each 2 DI) 1 F-DO (opt. for each 2 DO) | 6SL3246-0BA22-1BA0 | CU250S?2 DP | | | 6SL3246-0BA22-1PA0 | CU250S?2 PN | | - PROFIdrive
- PROFIsafe
- PROFIenergy
| 6SL3246-0BA22-1FA0 | - ODVA AC drive
- SINAMICS profile
| – | CU250S?2 CAN | | – | 6SL3246-0BA22-1CA0 | 1) SSM is possible only with PROFIsafe. Optional memory card with firmware V4.7 SP6 for CU230P?2, CU240E?2 and CU250S?2 Control Units Description | Suitable for | Article No. |
---|
SINAMICS SD card 512 MB + firmware V4.7 SP6 (Multicard V4.7 SP6) | CU230P?2 CU240E?2 CU250S?2 | 6SL3054-7TD00-2BA0 | Optional memory cards with licenses for CU250S?2 Control Units only Description | SINAMICS SD card 512 MB + licenses | SINAMICS SD card 512 MB + firmware V4.7SP6 (Multicard V4.7 SP6) + licenses | Licenses (without SD card) for upgrading license of an existing SD card |
---|
| Article No. | Article No. | Article No. |
---|
License Extended Functions Basic positioner (EPos) | 6SL3054-4AG00-2AA0-Z E01 | 6SL3054-7TD00-2BA0-Z E01 | 6SL3074-7AA04-0AA0 | License Extended Functions Safety (SLS, SSM, SDI) | 6SL3054-4AG00-2AA0-Z F01 | 6SL3054-7TD00-2BA0-Z F01 | 6SL3074-0AA10-0AA0 | Licenses Extended Functions Basic positioner (EPos) +Safety (SLS, SSM, SDI) | 6SL3054-4AG00-2AA0-Z E01+F01 | 6SL3054-7TD00-2BA0-Z E01+F01 | – | For additional information about firmware V4.7 SP6: https://support.industry.siemens.com/cs/document/109482094 Optional memory cards with firmware V4.6 or V4.7 for existing installations when service is required Description | Suitable for | Article No. |
---|
SINAMICS SD card 512 MB + firmware V4.6 (Multicard V4.6) | CU230P?2 CU240E?2 CU250S?2 | 6SL3054-7EG00-2BA0 | SINAMICS SD card 512 MB + firmware V4.7 (Multicard V4.7) | CU230P?2 CU240E?2 CU250S?2 | 6SL3054-7EH00-2BA0 | For an overview and more information on all available firmware versions, seehttps://support.industry.siemens.com/cs/document/67364620 Selecting the Power Module The optimum power unit can be quickly selected based on the required motor power, the supply voltage and the braking cycles to be expected. Power Modules in degree of protection IP20 are intended for installation in a control cabinet. PM240?2 and PM240 Power Modules – IP20 degree of protection PM240?2 Power Modules have an integrated braking chopper (four-quadrant applications) and are suitable for a large number of applications in general machinery construction. The same applies for PM240 Power Modules, but the PM240 Power Modules in frame size FSGX do not have an integrated braking chopper. A plug-in Braking Module is optionally available for this purpose. PM250 Power Modules – degree of protection IP20 PM250 Power Modules are suitable for the same applications as the PM240?2/PM240. Any braking energy is directly fed back into the line supply (four-quadrant applications – a braking resistor is not required). The Power Modules can be combined with the following Control Units: Control Units | Power Modules degree of protection IP20 |
---|
| PM240?2/PM240 | PM250 |
---|
CU230P?2 | ? | ? | CU240E?2 | ? | ? | CU250S?2 | ? | ? |  PM240, PM240?2 and PM250 Power Modules Rated power 1) | | Rated output currentIrated2) | PM240?2 Power Modules 3) Degree of protection IP20 All CUs pluggable | PM250 Power Module degree of protection IP20 All CUs pluggable |
---|
kW | hp | A | Article No. | Article No. |
---|
200 ... 240 V 1 AC/3 AC | 0.55 | 0.75 | 3.2 | 6SL3210-1PB13-0?L0 | – | 0.75 | 1 | 4.2 | 6SL321?-1PB13-8?L0 | – | 1.1 | 1.5 | 6 | 6SL3210-1PB15-5?L0 | – | 1.5 | 2 | 7.4 | 6SL3210-1PB17-4?L0 | – | 2.2 | 3 | 10.4 | 6SL321?-1PB21-0?L0 | – | 3 | 4 | 13.6 | 6SL3210-1PB21-4?L0 | – | 4 | 5 | 17.5 | 6SL321?-1PB21-8?L0 | – | 200 ... 240 V 3 AC | 5.5 | 7.5 | 22 | 6SL3210-1PC22-2?L0 | – | 7.5 | 10 | 28 | 6SL3210-1PC22-8?L0 | – | 11 | 15 | 42 | 6SL3210-1PC24-2UL0 | – | 15 | 20 | 54 | 6SL3210-1PC25-4UL0 | – | 18.5 | 25 | 68 | 6SL3210-1PC26-8UL0 | – | 22 | 30 | 80 | 6SL3210-1*-0UL0 | – | 30 | 40 | 104 | 6SL3210-1PC31-1UL0 | – | 37 | 50 | 130 | 6SL3210-1PC31-3UL0 | – | 45 | 60 | 154 | 6SL3210-1PC31-6UL0 | – | 55 | 75 | 178 | 6SL3210-1PC31-8UL0 | – | 380 ... 480 V 3 AC | 0.37 4) | 0.5 | 1.3 | – 4) | – | 0.55 | 0.75 | 1.7 | 6SL3210-1PE11-8?L1 | – | 0.75 | 1 | 2.2 | 6SL3210-1PE12-3?L1 | – | 1.1 | 1.5 | 3.1 | 6SL3210-1PE13-2?L1 | – | 1.5 | 2 | 4.1 | 6SL3210-1PE14-3?L1 | – | 2.2 | 3 | 5.9 | 6SL3210-1PE16-1?L1 | – | 3 | 4 | 7.7 | 6SL321?-1PE18-0?L1 | – | 4 | 5 | 10.2 | 6SL3210-1PE21-1?L0 | – | 5.5 | 7.5 | 13.2 | 6SL3210-1PE21-4?L0 | – | 7.5 | 10 | 18 | 6SL321?-1PE21-8?L0 | 6SL3225-0BE25-5AA1 | 11 | 15 | 26/25 | 6SL3210-1PE22-7?L0 | 6SL3225-0BE27-5AA1 | 15 | 20 | 32 | 6SL321?-1PE23-3?L0 | 6SL3225-0BE31-1AA1 | 18.5 | 25 | 38 | 6SL3210-1PE23-8?L0 | 6SL3225-0BE31-5?A0 | 22 | 30 | 45 | 6SL3210-1PE24-5?L0 | 6SL3225-0BE31-8?A0 | 30 | 40 | 60 | 6SL3210-1PE26-0?L0 | 6SL3225-0BE32-2?A0 | 37 | 50 | 75 | 6SL3210-1PE27-5?L0 | 6SL3225-0BE33-0?A0 | 45 | 60 | 90 | 6SL3210-1PE28-8?L0 | 6SL3225-0BE33-7?A0 | 55 | 75 | 110 | 6SL3210-1PE31-1?L0 | 6SL3225-0BE34-5?A0 | 75 | 100 | 145 | 6SL3210-1PE31-5?L0 | 6SL3225-0BE35-5?A0 | 90 | 125 | 178 | 6SL3210-1PE31-8?L0 | 6SL3225-0BE37-5?A0 | 110 | 150 | 205 | 6SL3210-1PE32-1?L0 | – | 132 | 200 | 250 | 6SL3210-1PE32-5?L0 | – | 160 3) | 250 | 302 | 6SL3224-0XE41-3UA0 | – | 200 3) | 300 | 370 | 6SL3224-0XE41-6UA0 | – | 250 3) | 400 | 477 | 6SL3224-0XE42-0UA0 | – | 500 ... 690 V 3 AC | 11 | 10 | 14 | 6SL3210-1PH21-4?L0 | – | 15 | 15 | 19 | 6SL3210-1PH22-0?L0 | – | 18.5 | 20 | 23 | 6SL3210-1PH22-3?L0 | – | 22 | 25 | 27 | 6SL3210-1PH22-7?L0 | – | 30 | 30 | 35 | 6SL3210-1PH23-5?L0 | – | 37 | 40 | 42 | 6SL3210-1PH24-2?L0 | – | 45 | 50 | 52 | 6SL3210-1PH25-2?L0 | – | 55 | 60 | 62 | 6SL3210-1PH26-2?L0 | – | 75 | 75 | 80 | 6SL3210-1PH28-0?L0 | – | 90 | 100 | 100 | 6SL3210-1PH31-0?L0 | – | 110 | 100 | 115 | 6SL3210-1PH31-2?L0 | – | 132 | 125 | 142 | 6SL3210-1PH31-4?L0 | – | Heat sink variant | | | ↑ | | Standard | | | 0 | | Push Through | | | 1 | | Integrated line filter | | | ↑ | ↑ | Without | (for IT systems) | | U | U | Class A | (for TN systems) | | A | A | Class B | (for TN systems) | | – | Integrated line filter not available, as external option only | 1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO). Low overload (LO) generally applies for applications with low dynamic response (continuous operation), quadratic torque characteristic with low break loose torque and low speed accuracy. Examples: Centrifugal pumps, radial/axial fans, rotary piston fans, radial compressors, vacuum pumps, chain conveyors, agitators. High Overload (HO) generally applies for applications with increased dynamic response (cyclic operation) and constant torque characteristics with high break loose torque. Examples: Gear pumps, eccentric worm pumps, mills, mixers, crushers, lifting/lowering gear, centrifuges. 2) The rated output current Irated is based on the duty cycle for low overload (LO). These current values are applicable for 200 V, 400 V or 690 V. 3) 160 kW ... 250 kW, PM240 Power Modules (frame size FSGX). 4) The PM240?2 Power Module with Article No. 6SL3210-1PE11-8. L1 corresponds to 0.37 kW (0.5 hp) with duty cycle HO. Data based on a duty cycle with low overload (LO). Data based on duty cycle with high overload (HO), see section Power Modules. Selecting optional system components Inligent Operator Panel IOP Graphic display with bar-type diagrams, e.g. for status values such as pressure or flowrate. User-friendly commissioning, diagnostics and local operator control using a large plain text display, clear menu navigation and application wizards. Inligent Operator Panel IOP Handheld A handheld version of the IOP can be ordered for use. In addition to the IOP, this includes a housing with rechargeable batteries, charging unit and RS232 connecting cable. Basic Operator Panel BOP-2 Menu navigation and 2-line display permit fast and user-friendly commissioning of the inverter. Simple basic commissioning by simultaneously displaying parameter and parameter value, as well as the option of filtering parameters. Door mounting kit for IOP/BOP?2 Using the optionally available door mounting kit, the IOP/BOP?2 can be mounted in a control cabinet door with just a few manual operations (IP54/UL Type 12 degree of protection is achieved). Push-through mounting frame for Push Through variants of the PM240?2 Power Modules It is advisable to use an optionally available mounting frame to install the push-through unit in a control cabinet. This mounting frame includes the necessary seals and frame to ensure compliance with degree of protection IP54. If the Power Module is installed without use of the optional mounting frame, the user is responsible for ensuring that the requisite degree of protection is provided. The kit contains all the necessary nuts and seals. Memory card The parameter settings for an inverter can be stored on the SINAMICS SD memory card. When service is required, e.g. after the inverter has been replaced, the drive system is immediay ready for use again. The memory card can also be used to upgrade the firmware of the Control Unit. Brake Relay The Brake Relay allows the Power Module to be connected to an electromechanical motor brake. This allows the motor brake to be controlled directly from the Control Unit. Safe Brake Relay The Safe Brake Relay allows the Power Module to be safely connected to an electromechanical motor brake, allowing the brake to be directly and safely controlled from the CU250S?2 Control Unit in accordance with IEC 61508 SIL 2 and EN ISO 13849?1 PL d and Category 3. PC inverter connection kit 2 For controlling and commissioning an inverter directly from a PC if the appropriate software (STARTER commissioning tool or SINAMICS Startdrive) has been installed. Shield connection kit for Power Modules The shield connection kit makes it easier to connect the shields of supply and control cables, provides mechanical strain relief and thus ensures optimum EMC performance. The shield connection kit is included in the scope of delivery of PM240?2 Power Modules, frame sizes FSA to FSF. Shield connection kit for Control Units The shield connection kit offers optimum shield connection and strain relief for all signal and communication cables. It includes a matching shield bonding plate and all of the necessary connecting and retaining elements for mounting.  Description | Article No. |
---|
Inligent Operator Panel IOP | | - German, English, French, Italian, Spanish, Portuguese, Dutch, Swedish, Russian, Czech, Polish, Turkish, Finnish
| 6SL3255-0AA00-4JA1 | - Chinese (simplified), English, German
| 6SL3255-0AA00-4JC1 | Operator Panel IOP Handheld | 6SL3255-0AA00-4HA0 | Operator Panel BOP?2 | 6SL3255-0AA00-4CA1 | Door mounting kit for IOP/BOP?2 | 6SL3256-0AP00-0JA0 | Push-through mounting frame | | - For PM240?2 Power Modules degree of protection IP20, Push Through variants
| | | 6SL3260-6AA00-0DA0 | | 6SL3260-6AB00-0DA0 | | 6SL3260-6AC00-0DA0 | Memory card | | - SINAMICS SD card 1)
512 MB
| 6SL3054-4AG00-2AA0 | Brake Relay | 6SL3252-0BB00-0AA0 | Safe Brake Relay | 6SL3252-0BB01-0AA0 | PC inverter connection kit 2 | 6SL3255-0AA00-2CA0 | Shield connection kits | | - For PM240?2 Power Modules
| | | Supplied with the Power Modules, available as a spare part | | | | 6SL3262-1AC00-0DA0 | | 6SL3262-1AD00-0DA0 | | 6SL3262-1AF00-0DA0 | | | - For CU230P?2 HVAC and CU230P?2 DP
| 6SL3264-1EA00-0FA0 | | 6SL3264-1EA00-0HA0 | - For CU230P?2 PN, CU240E?2 PN and CU240E?2 PN?F
| 6SL3264-1EA00-0HB0 | | 6SL3264-1EA00-0LA0 | STARTER commissioning tool 2) on DVD?ROM | 6SL3072-0AA00-0AG0 | SINAMICS Startdrive commissioning tool 3) on DVD?ROM | 6SL3072-4DA02-0XG0 | 1) Approved only for CU230P?2 HVAC and CU230P?2 DP Control Units with firmware version V4.6 and higher. 2) The STARTER commissioning tool is also available on the Internet at http://www.siemens。。com/starter 3) The SINAMICS Startdrive commissioning tool is also available on Internet athttps://support.industry.siemens.com/cs/document/68034568 Line-side power components The following line-side power components are available for SINAMICS G120 standard inverters: Line filters With one of the additional line filters, the Power Module attains a higher radio interference class. Line reactors (only for PM240?2 Power Modules, frame sizes FSA to FSC, and PM240 FSGX) Line reactors smooth the current drawn by the inverter and thus reduce harmonic components in the line current. Through the reduction of the current harmonics, the thermal load on the power components in the rectifier and in the DC-link capacitors is reduced as well as the harmonic effects on the supply. The use of a line reactor increases the service life of the inverter. Note: A DC link reactor is integrated in the PM240?2 Power Modules FSD to FSF and therefore no line reactor is required. Recommended line-side power components Furthermore, this is a recommendation for additional line-side components, such as fuses and circuit breakers (line-side components must be dimensioned in accordance with IEC standards). Additional information about the line-side power components can be found in Catalogs LV 10, IC 10 and IC 10 AO as well as the Industry Mall. DC link components The following DC link components are available for the SINAMICS G120 standard inverters: Braking resistors (for PM240 and PM240?2 Power Modules only) Excess energy in the DC link is dissipated in the braking resistor. The braking resistors are designed for use with PM240 and PM240?2 Power Modules. They are equipped with an integrated braking chopper (electronic switch). There is an optional plug-in Braking Module for frame size FSGX. Braking Module (for PM240 Power Modules, frame size FSGX only) A Braking Module and the matching external braking resistor are required to bring drives with a PM240 Power Module, frame size FSGX, to a controlled standstill in the event of a power failure (e.g. emergency retraction or EMERGENCY STOP Category 1) or to limit the DC link voltage during a short period of generator operation. The Braking Module houses the power electronics and the associated control circuit. Load-side power components The following load-side power components are available for the SINAMICS G120 standard inverters. This means that during operation with output reactors or sine-wave filters, longer, shielded motor cables are possible and the motor service life can be extended: Output reactors (not for PM240-2 Power Modules, frame sizes FSD to FSF, as these have an integrated DC link reactor) Output reactors reduce the rate of voltage rise (dv/dt) and the height of the current peaks, and enable longer motor cables to be connected. Sine-wave filters (not for PM240?2 Power Modules) Sine-wave filters limit the rate of voltage rise (dv/dt) and the peak voltages on the motor winding. Similar to an output reactor, they enable the connection of longer motor cables. Additional options Further selected supplementary products are available from Siemens Partners. Please select “Drive Options” as the technology in the "Solution Partner Finder” : http://www.siemens。。com/automation/partnerfinder Spare parts Spare parts kit for Control Units The spare parts kit contains small parts for all variants of the following SINAMICS G120 Control Units: - CU230P?2
- CU240E?2
- CU240E?2 F
- CU250S?2
Shield connection kits for PM240?2 Power Modules A shield connection kit is supplied as standard with PM240?2 Power Modules in frame sizes FSA to FSF. This shield connection kit is also available as a spare part. Replacement door for PM240 Power Modules, frame size FSGX A complete replacement door can be ordered for the PM240 Power Module, frame size FSGX. Terminal cover kits for frame sizes FSD to FSF The terminal cover kit includes a replacement cover for the connecting terminals. Terminal cover kits which are suitable for the PM240?2 and PM250 Power Modules are available. Replacement connectors for PM240?2 Power Modules A set of connectors for the line feeder cable, braking resistor and motor cable can be ordered corresponding to the frame size of the PM240?2 Power Module. Fan units for PM240?2 Power Modules The fans of PM240?2 Power Modules are designed for extra long service life. For special requirements, replacement fans are available that can be exchanged quickly and easily. Replacement fans for PM240 and PM250 Power Modules The fans of PM240 and PM250 Power Modules are designed for extra long service life. Replacement fans can be ordered for special applications. 
組態(tài)The following electronic configuring aids and engineering tools are available for the SINAMICS G120 standard inverters: Drive Technology Configurator (DT Configurator) within the CA 01 The interactive catalog CA 01 – the offline Industry Mall of Siemens on DVD?ROM – contains over 100 000 products with approximay 5 million possible drive system product variants. The Drive Technology Configurator (DT Configurator) has been developed to facilitate selection of the correct motor and/or inverter from the wide spectrum of drives. It is integrated in Catalog CA 01 as an add-on on DVD?ROM. Online DT Configurator In addition, the DT Configurator can be used on the Internet without requiring any installation. The DT Configurator can be found in the Siemens Industry Mall at the following address: http://www.siemens。。com/dt-configurator SIZER for Siemens Drives engineering tool The SIZER for Siemens Drives engineering tool makes it easy to engineer the SINAMICS drive family. It provides support when selecting the hardware and firmware components necessary to implement a drive task. SIZER for Siemens Drives is designed to support configuring of the entire drive system. You can find further information on the SIZER for Siemens Drives engineering tool in the chapter Engineering tools. The SIZER for Siemens Drives engineering tool is available free on the Internet at http://www.siemens。。com/sizer STARTER commissioning tool The STARTER commissioning tool allows menu-prompted commissioning, optimization and diagnostics. Apart from the SINAMICS drives, STARTER is also suitable for MICROMASTER 4 devices. You can find further information about the STARTER commissioning tool in the chapter Engineering tools. Additional information about the STARTER commissioning tool is available on the Internet at http://www.siemens。。com/starter SINAMICS Startdrive commissioning tool SINAMICS Startdrive is a tool for configuring, commissioning, and diagnosing the SINAMICS family of drives and is integrated into the TIA Portal. SINAMICS Startdrive can be used to implement drive tasks with the SINAMICS G110M, SINAMICS G120, SINAMICS G120C, SINAMICS G120D and SINAMICS G120P inverter series. The commissioning tool has been optimized with regard to user friendliness and consistent use of the TIA Portal benefits of a common working environment for PLC, HMI and drives. You can find further information on the SINAMICS Startdrive commissioning tool in the chapter Engineering tools. The SINAMICS Startdrive commissioning tool is available free on the Internet at http://www.siemens。。com/startdrive Drive ES engineering system Drive ES is the engineering system that can be used to integrate the communication, configuration and data management functions of Siemens drive technology into the SIMATIC automation world easily, efficiently and cost-effectively. Two software packages are available for SINAMICS – Drive ES Basic and Drive ES PCS. You can find further information about the Drive ES engineering system in the chapter Engineering tools. Additional information about the Drive ES engineering system is available on the Internet at http://www.siemens。。com/drive-es 
技術(shù)規(guī)范Unless explicitly specified otherwise, the following technical specifications are valid for all the following components of the SINAMICS G120 standard inverters. General technical specifications |
---|
Mechanical ambient conditions | Long-term storage acc. to EN 60721?3?1 | | - Inverters and components, frame sizes FSA to FSF 1)
| Class 1M2 | - Inverters and components, frame size FSGX 2)
| Class 1M2 | Transport acc. to EN 60721?3?2 | | - Inverters and components, frame sizes FSA to FSF2)
| Class 2M3 | - Inverters and components, frame size FSGX 2)
| Class 2M2 | Operation acc. to EN 60721?3?3 | | - Inverters and components, frame sizes FSA to FSF
| Class 3M1 | | Test Fc (sinusoidal) according to EN 60068?2?6 Deflection: 0.075 mm at 10 ... 57 Hz Acceleration: 10 m/s2 (1 × g) at 57 ... 150 Hz 10 frequency cycles per axis | | Test Ea (semi-sinusoidal) according to EN 60068?2?27 Acceleration: 49 m/s2 (5 × g) at 30 ms 3 shocks in all three axes in both directions | - Inverters and components, frame size FSGX
| | | Test Fc according to EN 60068?2?6 Deflection: 0.075 mm at 10...58 Hz Acceleration: 10 m/s2 (1 × g) at 58 ... 200 Hz | | Test Ea according to EN 60068?2?27 Acceleration: 98 m/s2 (10 × g) at 20 ms | Ambient conditions | Protection class acc. to EN 61800?5?1 | Class I (with protective conductor system) and class III (PELV) | Touch protection acc. to EN 61800?5?1 | For the intended purpose |
|