SMART Transmitter Power Supply KFD2-STV4-Ex1-1
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
- Output 0/1 V ... 5 V
- Terminals with test points
- Up to SIL 2 acc. to IEC 61508
德國倍加福代理商P+F現(xiàn)貨防爆隔離式K系列導(dǎo)軌式模擬量輸入安全柵KFD2-STV4-EX1-1
參數(shù)表節(jié)選:的技術(shù)參數(shù) KFD2-STV4-Ex1-1
產(chǎn)品闡述 | ||
---|---|---|
Input 0/4 mA ... 20 mA Output 0/1 V ... 5 V |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 1.5 W | |
Power consumption | 1.8 W | |
Input | ||
Connection | terminals 1+, 2-, 3 or 5-, 6+ | |
Input signal | 0/4 ... 20 mA | |
Voltage drop | ≤ 2.4 V at 20 mA (terminals 5, 6) | |
Input resistance | ≤ 64 Ω terminals 2-, 3 ; ≤ 500 Ω terminals 1+, 3 (250 Ω load) | |
Available voltage | ≥ 16 V at 20 mA terminals 1+, 3 | |
Output | ||
Connection | terminals 7-, 8+, 9 | |
Load | output resistance: 250 Ω | |
Output signal | 0/1 ... 5 V | |
Ripple | max. 12.5 mV | |
Transfer characteristics | ||
Deviation | at 20 °C (68 °F), 0/1 ... 5 V ≤ 5 mV incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage | |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB) | |
Rise time | 20 µs | |
Settling time | 200 µs | |
De-energized delay | 20 µs | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 200 g | |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 99 ATEX 7060 | |
Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC | |
EU-Type Examination Certificate | DMT 01 ATEX E 133 | |
Marking | I (M1) [Ex ia] I | |
Certificate | TÜV 99 ATEX 1499 X | |
Marking | II 3G Ex nA II T4 [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0173 (cULus) | |
IECEx approval | IECEx BAS 04.0016 IECEx CML 15.0055X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA IIC T4 Gc |
德國倍加福代理商P+F現(xiàn)貨防爆隔離式K系列導(dǎo)軌式模擬量輸入安全柵KFD2-STV4-EX1-1
KFD2-STV4-EX1-1
緊湊型電源 | 通用電源模塊 | 導(dǎo)軌式電源模塊 |
HCD2-FBPS-1.23.500 | FBTA-228-BPFB-8 | USB-FBPS-1.11.45.NI |
HCD2-FBPS-1.500 | FBTA-228-BPFB-R-4R | KLD2-FBPS-1.12.220 |
HD2-DM-A | HD2-DM-A | KLD2-FBPS-1.25.360 |
HD2-DM-A.RO | HD2-DM-A.RO | KLD2-PC-1.1.IEC |
HD2-DM-B | HD2-DM-B | KLD2-PR-1.IEC |
MBHC-FB-4* | HD2-FBPS-1.17.500 | KLD2-PR-Ex1.IEC |
MBHC-FB-4.GT | HD2-FBPS-1.23.500 | KLD2-PR-Ex1.IEC1 |
MBHC-FB-4.HSC* | HD2-FBPS-1.25.360 | |
MBHC-FB-4.YO* | HD2-FBPS-1.500 | |
MBHC-FB-4R* | ||
MBHC-FB-4R.HSC* | ||
MBHC-FB-4R.YO* | ||
MBHC-FB-8R* | ||
MBHC-FB-8R.HSC* | ||
MBHC-FB-8R.RH* | ||
MBHC-FB-8R.YO* |
KFD2-STV4-EX1-1
KFD2-STV4-EX1-1
SMART Transmitter Power Supply KFD2-STV4-Ex1-1
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
- Output 0/1 V ... 5 V
- Terminals with test points
- Up to SIL 2 acc. to IEC 61508