HKA-F6系列霍爾電流傳感器的初、次級(jí)之間是絕緣的,可用于測(cè)量直流、交流和脈沖電流。
(HKA-F6 Series Hall-effect Current Sensor between primary and secondary is insulated, can be used for the measurement of DC, AC and pulse current)
電氣參數(shù)(Electrical characteristics) 型號(hào)Type HKA5000 -F6 HKA10000 -F6 HKA20000 -F6 HKA30000 -F6 A Ipn 額定輸入電流 Rated input 5000 10000 20000 30000 A Ipm 測(cè)量電流范圍 Measuring range 6000 12000 24000 36000 A Vout 輸出電壓 Rated output voltage 4 V Vo 零電壓失調(diào) Zero offset voltage <±25 mV VOM 磁失調(diào)電壓 Magnetic offset voltage ≤±25 mV RL 負(fù)載電阻 Load resistance ≥10 KΩ Vc 電源電壓 Supply voltage ±15±5% V Ic 靜態(tài)功耗 Current consumption ≤50 mA Vot 零點(diǎn)溫漂 Thermal drift of Vo ≤±0.5 mV/℃ F 帶寬 Frequency bandwidth(-3dB) DC~5 KHz εG 精度 Accuracy ±1 % εL 線性度 Linearity ±1 % Tr 響應(yīng)時(shí)間 Response time ≤7 μS Vd 絕緣電壓 Insulation voltage 6 KV Ta 工作溫度 Ambient operating temperature -40~+85 ℃ Ts 儲(chǔ)存溫度 Ambient storage temperature -40~+125 ℃ M 重量 mass 6200 g 標(biāo)準(zhǔn)Standards EN50178/IEC61010-1/UL94-Vo/ROHS
使用說(shuō)明Remarks
1、 應(yīng)用:通訊電源、不間斷電源UPS、斬波器、電化學(xué)、整流、電源監(jiān)測(cè)、電焊機(jī)、變頻、開(kāi)關(guān)電源、電池監(jiān)測(cè)、電動(dòng)機(jī)監(jiān)測(cè)等領(lǐng)域。Application: communication power supply, uninterruptible power supply UPS chopper, electrochemical, rectifier, power monitoring, welding machines, inverter, switching power supply, battery monitoring, motor monitoring fields.
2、傳感器的輸出幅度可根據(jù)用戶需要進(jìn)行適當(dāng)調(diào)節(jié)。The amplitude of the output of the sensor can be appropriately adjusted according to user needs.
3、可按用戶需求定制不同額定輸入電流和輸出電壓的傳感器。Custom different rated input current and the output voltage of the sensor.
下載詳細(xì)資料HKA-F6.pdf