SIGNAL ISOLATION 3 OUTPUT CONVERTER
- Operating humidity : 90%RH Max
(none condensing)
- Power supply
AC : 110V or 220V/60Hz ±10%,approx 3VA
DC : 18V ~ 30V ±10%,approx 3VA
- Power selection : AC 110V/220V Swich
in the back plane
- Mounting : Wall or DIN rail
- Accuracy : ± 0.2%
- Temp'coefficient : ±0.015/℃
- Response time : 0.5 Sec or less(0~90%)
- Insulation resistance : 100MΩor more
with 500VDC(Input/Output/Power)
- Dielectric strength : 1500VAC at 1minute
(Input to Output to Power)
1 : DC Voltage
2 : DC Current
3 : RTD Sensor
4 : Potentiometer
O : Other special spec.
CDI TECH CO.,LTD.
MODEL CDI - SIC3
SIGNAL ISOLATION 3 OUTPUT CONVERTER
GENERAL SPECIFICATION
◆DC VOLTAGE
- Range : ± 300V Max
- Resistance : 20KΩMin at ± 1V
1MΩMiN at ±10V
◆DC CURRENT
- Range : 50mA Max
- Resistance : 250ΩMax
◆RTD SENSOR ; -200∼ 600℃
◆POTENTIOMETER ; 100Ω∼100KΩ
- DC VOLTAGE : ±12V Max
- Load Resistance
Output Resistance
0 ~ 10mV 1KΩor more
0 ~ 100mV 1KΩ or more
0 ~ 1V 1KΩ or more
0 ~ 5V 2KΩ or more
0 ~ 10V 4KΩ or more
-10V ~ 10V 4KΩ or more
- DC CURRENT : 0 ~ 20mA
- Load Resistance
Output Resistance
0 ~ 1mA 15KΩor less
0 ~ 10mA 1.5KΩ or less
0 ~ 20mA 750Ω or less
1 ~ 5mA 3KΩ or less
4 ~ 20mA 750Ω or less