PSOCR-ST-1S-3E PSOCR-ST-1S-2E PSOCR-ST-1S-1E電子過流繼電器
Type : PSOCR-ST-1S Type
▷ Preciseness, Safety guaranteed with the adoption of Micro Controller
▷ Installation space can be secured with its small size (48 x 52 x 82)
▷ Wiring work is easy with its Tunnel structure (dia. 12.0mm)
▷ Easy to repair with the subdivision (4~8 LER adopted) of trouble details.
▷ Actual current can be checked by the adoption of Alert Flickering LED.
▷ Din Rail (35mm) & Bolting (4.0mm) available
▷ Refined design
NO | Type | PSOCR-ST-1S-3E | PSOCR-ST-1S-2E | PSOCR-ST-1S-1E | |
1 | Rate Current | 05A | 0.5 ~ 12.0(A) | 5 ~ 60(A) | |
60A | 5 ~ 60(A) | ||||
2 | D - TIME | 1.0 ~ 25(s) | |||
3 | O - TIME | 1.0 ~ 25(s) | |||
4 | RESET | Manual OR POWER OFF | |||
5 | Operating Time Characteristics | Indefinite Time / Definite Time | Indefinite Time / Definite Time | Definite Time | |
6 | Operating Voltage | 110V | 110V ± 10% | ||
220V | 220V ± 10% | ||||
7 | Aux. Contact | 1C DRY CONTACT 250VAC 10A Resistive load |
NO | Type→ Indication & Operation↘ Indication & Protective operation↓ | PSOCR-ST-1S-3E | PSOCR-ST-1S-2E | PSOCR-ST-1S-1E | |||||||
LED NO. | Operating Time | LED NO. | Operating Time | LED NO. | Operating Time | ||||||
1 | Overcurrent | Definite Time | ○ | L7 | ○-TIME | ○ | L7 | ○-TIME | ○ | L7 | ○-TIME |
Indefinite Time | Indefinite Time curve | Indefinite Time curve | × | NONE | |||||||
2 | Single Phase | R | ○ | L4 | Within 2.0 sec | ○ | L4 | Within 2.0 sec | ○ | L4 | Within 2.0 sec |
S | ○ | L6 | ○ | L6 | ○ | L6 | ○-TIME | ||||
T | ○ | L8 | ○ | L8 | ○ | L8 | Within 2.0 sec | ||||
3 | Locked motor | ○ | L5 | Within 2.0 sec(Definite Time) | ○ | L5 | Within 2.0 sec(Definite Time) | ○ | L5 | Within 2.0 sec(Definite Time) | |
4 | Plugging | ○ | L3 | 1.0s | × | L3 | NONE | × | L3 | NONE | |
5 | ALERT | ○ | L2 | More than 90% of Trip Current | ○ | L2 | More than 90% of Trip Current | ○ | L2 | More than 90% of Trip Current | |
6 | POWER ON | ○ | L1 | Power On | ○ | L1 | Power On | ○ | L1 | Power On | |
7 | DIP S/W 1 | Indefinite Time/Definite Time | Indefinite Time/Definite Time | 05A/60A | |||||||
8 | DIP S/W 2 | C.W./C.W.+C.C.W. | LOCKING/NO LOCKING | LOCKING/NO LOCKING |