MR-DMS直流信號報警DC signal alarm setter
[MR-RMS] RTD temperature alarm setter (2alarm)
[MR-PMS] Potentiometer alarm setter (2alarm)
[MR-TMS] Thermocouple alarm setter (2alarm)
[MR-DMS4] DC signal alarm setter (4alarm)
[MR-RMS4] RTD temperature alarm setter (4alarm)
This is a converter used for requiring contact output
in response of high & lower setting values at 2points
by inputting DC signal.
FEATURES
Small size(mm) : 83(H), 51(W), 102(D).
Isolation : input to output to power supply.
Power supply : AC or DC supply.
Wiring : terminal socket wiring.
Case & color : black ABS plastic case.
Weight : about 400g
MR - DMS
INPUT SIGNAL SPECIFICATION
OUTPUT SIGNAL SPECIFICATION
Output type : dry contact or specify.
Output range : 120VAC @ 1A, 30VDC @ 1A.
Dead band : 1% of full scale.
GENERAL SPECIFICATION'S
Operating ambient temperature : 0 - 50'C.
Non operating ambient temperature : -20 ~ 80'C.
Temperature coefficient : 0.015%/'C.
Operating ambient humidity : 90% RH max.(non condensing)
Insulation resistance : greater than 100Mohm with 500VDC.
Dielectric strength : 1500VAC @ 1minute (input to out1 to out2 to power).
Adjustment range : 0 - 99% (low & high).
Conversion accuracy : 0.2% max.
Response time : 0 - 90%(0.5sec).
Dead band error : 1% max.
Input voltage signal : -300 ~ 300VDC
Input voltage impedance : 1Mohm min.
Input current signal : 30mADC max.
Input current load resistance : 100ohm max. (at 20mA)
DISPLAY
Type : 3 digit FND
Display font : red super bright
Display function's : input or percent(%).
Display error : 1digit(LSB).
DISPLAY SIGNAL
1 : Input signal
2 : Percent(%)
OUTPUT SIGNAL
1 : Dry contact
2 : Specify
ALARM SET CONTACT
INPUT SIGNAL
DC SIGNAL
2(+), 3(-)
L > INPUT < H
L < INPUT < H
L < INPUT > H
L > INPUT > H
LOW SET
DRY CONTACT
5(B), 6(C), 7(A)
ON
OFF
OFF
ON
HIGH SET
DRY CONTACT
8(A), 9(C), 10(B)
OFF
OFF
ON
ON
This is a converter used for requiring contact output
in response of high & lower setting values at 2points
by inputting DC signal.