| | | | The earth leakage detector, approved under section 2 and 3, Article 24 of the regulations relative to the enforcement of the Fire Service Act, is a state-of-the-art digital multi-circuit detector developed for the purpose of preventing fires that may be started by electric shocks or electric leakages caused by the poor insulation of electric equipment on the side where the bifurcation load occur in AC circuits below 600V. The detector consists of visual current transformers (special ZCT) and electric leakage detector. It has been designed to respond according to accurate electric leakage values obtained by blocking the various types of noises, which are present in input signals, with an analog and digital
| | | | filterand only by converting normal signals. It has an in-built 16 bit micro-processor and can store the operating status of each circuit and time period (second/minute/day/month/year) up to 10 times. The central monitoring PC can monitor each circuit's status with a communication system, and up to 32 devices can be connected through in-built RS485 ports. The communication line can be extended up to 1km and an included monitoring software allows to connect to PC through RS485/RS232 interfaces. | | | Part Name | Earth Leakage Detector and Relay | Model | D2K-ED08 | D2K-ED16 | D2K-ED24 | D2K-ED32 | Certificate No | 누수 01-6 | 누수 01-5 | Circuit | 8 Circuit | 16 Circuit | 24 Circuit | 32 Circuit | Aux. power | AC 110/220 ±15%, 50/60Hz (Default), DC 110/125 ±20%(Option), | Rated current | AC 200mA~1000mA (100mA Step), Default-0.5A | Operating time | 0.1~3.0sec/0.1 ±50ms, 0.2~3.0 ±15%(0.1sec, Step), Default-0.2sec | Operating current | Set of 53%~75% | Non operating zone | Setting current of 52%-30sec over | Rated current ZCT | 200mA/100mV (75~125mV at 2㏀ Resistance) | Contact | 1a(All circuit) | 1a(All circuit) | 8a(ED08) | 16a(ED16) | 24a(ED24) | 32a(ED32) | Display | L.C.D display (20CharacterX4Line) | Key-pad | Mode, ESC, Enter, Direction Key(←,↑,→,↓) | Indicator | RUN (Green): C.P.U Error 동작상태 감시 AUTO (Yellow): 동작 후 Relay 및 Lamp의 복귀 [On(Flicker): Auto/On: Manual] BUZZER (Yellow): 동작 시 Buzzer 울림 [Off(Flicker)시: 꺼짐/On: 울림] COMM (Yellow): 깜박일 때 신호 출력 중 ZCT (Red): ZCT 연결 불량 및 연결이 되지 않았을 경우 PICK (Red): Pick-up 누전전류 동작 시 점등 SYS (Red): 내부회로 및 소자 불량 시 점등(System Error) ALARM (Red): 누전에 의한 동작표시기 | Fault Memory | 최근 사고치 10회 Memory 가능 및 사고선로별 회로표시 (“1”이 가장 최근 사고를 표시함) | Reset | Auto Reset / Manual Reset 가능(Program에 의하여 선택 방법) | Temperature | Operating temperature -10℃~60℃ Storage temperature -20~70℃ | Mounting | Flush mounted type | Contact capacity | AC 250V 5A 0.5sec (L/R=0) | Buzzer | 75dB 이상 (1m) | Insulation resistance | 1st-ground / 2nd-ground / 1st-2nd: 100㏁ or more DC 500V Megger | Withstand voltage | 1st-ground: AC 1,500V 2nd-ground: AC 500V 1st-2nd: 100㏁ or more: AC1,500V | Lightning impulse withstand voltage | Aux. power-ground 1.2㎲ x 50㎲ X 60kV Positive/Negative elevtronics. 3times | Vibration | Vibration frequency: 16.7Hz Double amplitude: 0.4mm Direction: horizontal, Vertical, transverse | Shock | Shock acceleration: 50G Shock application direction horizontal, vertical, transverse Shock time: 3times | Weight | 5Kg | 7Kg | | | | | 1Digital Earth Leakage Detector and Relay D2K-ED 1contents: The earth leakage detector, approved under section 2 1and 3, Article 24 of the regulations relative to the enforcement of 1the Fire Service Act, is a state-of-the-art digital multi-circuit 1detector ... |