| | | | DOV. DUV type voltage relay is induction rotary disk type and protects the power and distribution line & equipmets from abnormal voltage of AC circuit | | | | | OVR, OVGR Item | DOV Typeover voltage relay(OVR,OVGR) | DUV Type Under Voltage relay (UVR) | Operating value | ±5%of setting tap | ±5% of setting tap | Rrsetting value | above 90% of operating value in minimum tap(OVGR:80%) | below 110% of operating value in maximum tap | Operating value | Min voltage tap at lever #10 Input | Operating time (SEC) | 120% 130% 150% | 26.6 ±20% 17.7 ±18% 9.84 ±15% | Refer to characteristics wave of tested operating time (Fig 14) | Max. voltage tap at lever #10 Input | Operating time(SEC) | 80% 0% | 20.7 ±20% 7.4 ±10% | Refer to characteristics wave of Tested operating time (Fig 15) | Self temperatuer rising characteristics | At min tap Lever #1 the operating erro between normal condition and self temperature rising condition will be ±5% of setting tap value | The operating error will be ±5% of setting tap value | Temperature characteristics | 1. operating value: Min TAP. Lever #1 -10℃,50%℃ Error ±10% 2. operating time: Min TAP, Lever #10 Input | operating time (SEC) | 120% 130% 150% | 26.6 ±30% 17.7 ±37% 9.84 ±32% | | 1. operating value: Min TAP, Lever #1 -10℃,50℃ Error ±7% 2. operating time: Min TAP, Lever #10 Input | Operating time(SEC) | 80% 0% | 20.7 ±30% 7.4 ±15% | | Overload withstand | At min tap, 1.15 times 3hours of rating voltage | Vibration characteristics | In case of 10 minutes of vibration to each direction front and back, left and right, above and below in frequency 16.7Hz width 0.4mm in condition of min tap, lever # 110% of DOV type relay setting values 90% of DUV type relay should be good | shock Characteristics | In case of impacting 30g weight to all partsuf relay, all parts of relay should be good | Insulation characteristics | All circuit to case : over 10MΩ/50/00V Megger circuit to cireuit : over 10MΩ/500V Megger Contact to contact : Over 10MΩ/500V Megger | Withstand voltage | All ciruit to case : AC 2000V/1 minute Circuit to circuit : AC 1000V/1 minute contact to contact : AC 1000V/1 minute | contact capacity | Main contact : AC 110V 5A AC 110V 10A ICS contact : AC 110V 10A AC 110V | | | | | 1 Over and Under(Ground)Voltage Relay[59/27/64] DUV, 1DOV, DVG 1contents: 1.Multi type earth leakage detector has alarm or CB trip 1function with detecting multi circuit leakage. 12.As equipped with MCU (A/D converter) at main circuit, it is Over current relay(O.C.R)) is perated on overload and short circuit. This relay has two elements: one is definitive element for operating and indicating on fault of overload. the other is instantaneous element for operating and indicating in rush current on fault of short circuit. And then this relay is designed that. it is easy to detect a reason of fault and toresponse to what fault is some trouble
DCG/DOG type ground over current relay is induction rotary disk type that is operated in remained circuit current of current transformer | | | | | Item | Definitive element(ICS) | Instantaneous element(IIT) | Operating value | below ±5% of each setting value | below ±10% of each setting value | Resetting value | on time Lever 10, Over 90% of minimum current setting value | over 10% of minimum current setting vlue | operating time very Inverse | OPERATING TIME | DCO-B | TIME LEVER | OVER CURRENT (SEC) | TIME ERROR(%) | | 300% | 500% | 1000% | 300% | 500% | 1000% | # 10 | 5.0 | 2.3 | 1.4 | ±12 | ±7 | ±7 | # 7 | 3.5 | 1.6 | 0.98 | ±10 | ±6 | ±6 | # 4 | 2.0 | 0.92 | 0.56 | ±8 | ±5 | ±5 | DOC-B | # 10 | 4.0 | 1.6 | 0.76 | ±12 | ±7 | ±7 | # 7 | 2.8 | 1.12 | 0.53 | ±10 | ±6 | ±6 | # 4 | 1.6 | 0.64 | 0.3 | ±8 | ±5 | ±5 | | below 40mS in input 200% | Inertia characteristics | current setting minimum time setting 1000% of tap #10 value operating time: over 80% of nominal operating time | temperature characteristics | below ±20% in -20℃~+60℃ (Operating time: measuring in 300% of input current) | overload characteristics | Two times during 0.25 second in twenty times (100A) of rated current (operating value and time: minimum tap) | vibration characterstics | In case of two times of vibration to each direction 4 front and back, left and right, above and below) in frequeney 16.7hz, with 0.4mm in condition of 80% value of minimum seifty operating current, all parts of relay should be good | Impacting characterstics | In case of impacting two times 30g weght to all parts, all parts of relay should be good | Insulation resistor | over 10MΩ by DC 500V Megger in condition of all circuit to cubicle, contact to contact, and circuit to circuit | Dielectric voltage | AC 2000 1 minute common frequency in condition of all circuit to case, circuit to circuit AC 1000 1minute common frequency in condition of contact to contact | contact capacity | Main Contact AC 220/10A AC 110/15A Contacting time : 0.5 sec | | | Time Characteri-stics | Type | Model No | Rating | Tap Range (A) | IIT Unit (A) | Burden (VA) | Operrating Burden | ICS Unit (DCA) | Weight (kg) | A | Hz | ICS | ICS+IIT | Very inverse | Non- Drawout | DCG-B | CI5 | 1 | 60 | 0.5/2.5 | 10-40 | 12 | 2.5 | 20 | 1.0 | 3.0 | Drawout | DCG-B | CID5 | 12 | 2.5 | 20 | 0.5/2.0 0.1/1.0 | 4.0 | Non-Drawout | DOG-B | CI5 | 6.5 | 1.6 | 7 | 1.0 | 3.0 | Drawout | DOG-B | CID5 | 6.5 | 1.6 | 7 | 0.5/2.0 0.1/1.0 | 4.0 | | | |