| | | | The Auto- reclosing relay is designed with micro processor based electronic CPU, which can be applied for any distribution line either coordinating with synchronizing relay or bus voltage supervising relay. As setting range is wide, the reclosing relay may coordinate with other protective relay or system easily. Since the relay has a self checking. it can be shown the error message on the front plate df the reley as soon as detected. There is s delay timer which discrepanoy time detween main and aux. contact of circuit breaker con be adjusted. | | | | | Model | DRC-041 (Draw out type) DRC-041E (Draw out type) | Ratings | Aux. Power : DC110/125V(+99%, -20%) | Setting Range | Prepare Time : 30+(5, 10, 20, 40, 75) ∑ (5sec step, 30~180sec) Reclaim Time : 20+(10, 20, 40, 80, 130) ∑ (10sec step, 20~300sec) Waiting Time : 1,,2, 4, 5, 8 + ∑ (1sec step, 1~20sec) T1 Time : 0.1, 0.2, 0.4, 0.8, 1.5 + ∑ (0.1sec step, 0~3.0sec) T2 Time : 1, 2, 3, 4, 8, 15 + ∑ (1sec step, 0~300sec) T3 Time : 5, 10, 15, 30, 60 + ∑ (5sec step, 0~120sec ) | Input Contact | 25-a : Synchro Relay ( Normal “a”) M/L : Manual Locking 63CB : Circuit breaker Pressure 50/51-a : Relay Contact 43RC : Reclosing switch ON/OFF CB-a : Circuit breaker “a” Contact | Output Contact | 79B : OLTC Blocking 79M :Reclosing signal (During Reclosing pluse with) 79S : 50 Relay Blocking (During Reclosing pluse with) 79C : Relay Error (C.P.U. Power) 79F : Lock out (Fall) Continuous | Counter Indicator | Cumulative number of reclosing Commands. up to 999 | Reclosind pulse with 500ms | | Funtion | Test Counter erase Set Checking (Pt, Rt, Wt, T1, T2, T3, Counter) Reset (Lock out) CPU Reset | Permissible ambient Temperature | -10℃ to +50℃ (Guaranted Performance) -20℃ to +60℃ (Storage) | | Rating | 1Input 1Frequency 1Auxiliary Voltage 1Temperature | 1AC 5A (OC/EF) 50/60Hz ±5% DC 110V / DC 125V 1(DC±30%, AC±20%) -10℃ to +60℃ | Burden | 1AC Overcurrent 1AC Earth Fault 1AC Aux. Voltage 1DC Aux. Voltage | 10.3VA at In 0.3VA at In 10VA 8W | Current Setting | 1-OC- 1Overcurrent range 1Instantaneous range 1Operating value 1-EF- 1Overcurrent range 1Instantaneous range 1Operating value | 12 to 13.1A (steps of 0.1A) 20 to 83A (steps of 1A) 99% 1(±5%) 0.5~2.0A (steps of 0.1A) 5~50A (steps of 1A) 199% (±5%) | Time Setting & Curve | 1Overcurrent time Lever
1Definite time
1Long very inverse time
1Normal inverse time
1Very inverse time
1Extermely inverse time
1[according to IEC255-3.ES]
| 10.1~15(steps of 0.1)
1※I : Fault current(CT 2’ry) 1※IP : Setting Value ※tp : time lever | Contacts | 1Output Relay 1Trip & Alarm contact capacity 1Make 1Break 1Short current 1Digital Communication 1Transmission
| 1OC : Trip 1c Alarm 1a EF : Trip 1c Alarm 1a 1AC 240V 10A (L/R=0ms) DC 1000W 0.5sec (L/R=0ms) 1AC 240V 3a (L/R=0ms) DC 30W 0.5sec (L/R=0ms) 80In RS-232-C(option) | Insulation to IEC 255-5 | 1Dielectric Withstand 1RS232C 1Insulation resistance at 500V 1Impulse Voltage Withstand 1(except RS-232-C Socket) 1Surge transient simulator 1Electromagnetic 1Interference 1Weight
| 12kV for 1minute between all terminals and case earth 1500V for minute between Output >100㏁ 5kV-1.2/50㎲ 2.5kV 1㎒/200Ω[IEC255-6] 5W-Transceiver 150㎒, 400㎒ 10.3m 4.5㎏ | | | | | |