HBA-SP系列霍爾電流傳感器的初、次級(jí)之間是絕緣的,可用于測(cè)量直流、交流和脈沖電流。
(HBA-SP Series Hall-effect Current Sensor between primary and secondary is insulated, can be used for the measurement of DC, AC and pulse current)
電氣參數(shù)(Electrical characteristics) | |||||||
型號(hào) Type | HBA5- SP | HBA10- SP | HBA15- SP | HBA30- SP | HBA50-SP |
| |
Ipn | 額定輸入電流 Rated input | 5 | 10 | 15 | 30 | 50 | A |
Ipm | 測(cè)量電流范圍 Measuring range | 10 | 20 | 30 | 60 | 100 | A |
Rm | 測(cè)量電阻 Measuring resistance | 200-400 | Ω | ||||
KN | 匝比 Turns ratio | 4:1000 | 2:1000 | 2:1500 | 1:1500 | 1:2500 | |
Iout | 輸出電流 Rated output current | 20 | mA | ||||
Rs | 輸入管腳尺寸 Input pin size | φ0.8 | φ1.0 | φ1.0 | φ1.6 | 2×□1.6×1.5 |
|
Io | 零電流失調(diào) Zero offset current | <0.2 | mA | ||||
Vc | 電源電壓 Supply voltage | ±15±5% | V | ||||
Ic | 靜態(tài)功耗 Current consumption | ≤10+Iout | mA | ||||
Iot | 零點(diǎn)溫漂 Thermal drift of Io | ≤0.005 | mA/℃ | ||||
F | 帶寬 Frequency bandwidth(-3dB) | DC~150 | KHz | ||||
εG | 精度 Accuracy | ±0.5 | % | ||||
εL | 線性度 Linearity | ±0.1 | % | ||||
di/dt | 跟隨精度Accurately followed | >50 | A/μS | ||||
Tr | 響應(yīng)時(shí)間 Response time | ≤1 | μS | ||||
Vd | 絕緣電壓 Insulation voltage | 5.0 | KV | ||||
Ta | 工作溫度 Ambient operating temperature | -40~+85 | ℃ | ||||
Ts | 儲(chǔ)存溫度 Ambient storage temperature | -40~+125 | ℃ | ||||
M | 重量 mass | 15 | g | ||||
標(biāo)準(zhǔn)Standards | EN50178/IEC61010-1/UL94-Vo/ROHS |
使用說(shuō)明Remarks
1、 應(yīng)用:通訊電源、不間斷電源UPS、斬波器、電化學(xué)、整流、電源監(jiān)測(cè)、電焊機(jī)、變頻、開關(guān)電源、電池監(jiān)測(cè)、電動(dòng)機(jī)監(jiān)測(cè)等領(lǐng)域。Application: communication power supply, uninterruptible power supply UPS chopper, electrochemical, rectifier, power monitoring, welding machines, inverter, switching power supply, battery monitoring, motor monitoring fields.
2、傳感器的輸出幅度可根據(jù)用戶需要進(jìn)行適當(dāng)調(diào)節(jié)。The amplitude of the output of the sensor can be appropriately adjusted according to user needs.
3、可按用戶需求定制不同額定輸入電流和輸出電壓的傳感器。Custom different rated input current and the output voltage of the sensor.
HBA-SP.pdf