Capacity (kVA) | % lmp. | Efficiency (%) | Dimension(㎜) | Weight (kg) | |||||
W | D | H | A | B | C | ||||
100 | 6 | 97.4 | 1208 | 648 | 1213 | 414 | 988 | 548 | 640 |
200 | 6 | 97.6 | 1213 | 748 | 1398 | 417 | 1016 | 648 | 880 |
300 | 6 | 98.1 | 1323 | 748 | 1453 | 453 | 1088 | 648 | 1180 |
400 | 6 | 98.2 | 1428 | 848 | 1483 | 488 | 1158 | 748 | 1420 |
500 | 6 | 98.4 | 1478 | 878 | 1568 | 506 | 1194 | 788 | 1620 |
600 | 6 | 98.5 | 1563 | 958 | 1628 | 534 | 1276 | 878 | 1960 |
750 | 6 | 98.5 | 1658 | 958 | 1768 | 565 | 1338 | 878 | 2300 |
1000 | 6 | 98.7 | 1778 | 958 | 1888 | 606 | 1420 | 878 | 2890 |
1500 | 6 | 98.9 | 1948 | 998 | 1903 | 662 | 1326 | 878 | 3970 |
2000 | 6 | 98.9 | 2078 | 1218 | 2048 | 705 | 1412 | 1108 | 4710 |
※ The above are subject to change without notice.
Capacity (kVA) | % lmp. | Efficiency (%) | Dimension(㎜) | Weight (kg) | |||||
W | D | H | A | B | C | ||||
200 | 7 | 97.5 | 1548 | 848 | 1398 | 523 | 1228 | 748 | 1370 |
300 | 7 | 97.9 | 1648 | 848 | 1478 | 558 | 1298 | 788 | 1720 |
500 | 7 | 98.4 | 1738 | 848 | 1543 | 593 | 1368 | 788 | 2210 |
600 | 7 | 98.5 | 1763 | 958 | 1723 | 598 | 1378 | 878 | 2450 |
750 | 7 | 98.6 | 1863 | 958 | 1733 | 633 | 1473 | 878 | 2840 |
1000 | 7 | 98.6 | 1888 | 958 | 1873 | 643 | 1493 | 878 | 3330 |
1500 | 7 | 98.8 | 2083 | 1218 | 1993 | 708 | 1583 | 1108 | 4510 |
2000 | 7 | 98.8 | 2173 | 1218 | 2183 | 738 | 1643 | 1108 | 5590 |
2500 | 6.5 | 99.0 | 2328 | 1248 | 2308 | 793 | 1898 | 1108 | 7200 |
3000 | 6.0 | 99.1 | 2508 | 1348 | 2328 | 853 | 2018 | 1108 | 9020 |
4000 | 6.3 | 99.2 | 2633 | 1368 | 2418 | 893 | 2098 | 1108 | 10780 |
5000 | 6.5 | 99.3 | 2708 | 1398 | 2898 | 918 | 2163 | 1108 | 13230 |
※ The above are subject to change without notice.
▶ACCESSORIES |
● Name Plate |
Made of stainless, showing specifications of rating, wiring method and placed on the top of transformer |
● High & Low Voltage Terminal |
Located on the surface of wiring and top of transformer. As high voltage terminal is a terminal of maintaining a fixed angle, that is easy to be connected with cable |
● Temperature Indicator |
Detecting temperature of coil and indicating on a digital thermometer installed in panel. Inputting the temperature into the controller and the current temperature is always shown. If rising more than input temperature, and then releasing alarm signal ! If needed, sending signal of circuit construction |
● Lifting Lug / Danger Mark |
Easy to install and transport, safety mark attached |
● Cooling Fan |
If required, the cooling fans are installed in the lower part of transformer and operated by single phase AC 220V or 110V |