Two wire 4~20mA current output signal
RTD inputs
Measuring ranges from -50 to 400°C
Loop powered 4~20mA with LED local
display
Explosion protection Ex d IIC T6
Excellent accuracy and long term
stability
Applications
These are recommended in applications
requiring amplification of RTD signals to
carry to a long distance or guard against
heavy field electrical noise.
The transmitter converts RTD inputs to
an analog signal for direct interface with
indicators, recorders, controllers, PLC, DCS
systems can be used for a wide range
ofapplications in process control, automatic
machinery and hydraulic or pneumatic
system design.
into standard weather or explosion-proofed terminal
heads used on RTD assemblies to provide a
4~20mA transmission signal. It is a cost effective
solution for all temperature measurement and accurate,
durable and reliable. Numerous configurations for
measurement in many different mediums are offered.
Generally the transmitter produces a linear 4~20mA
output carried on a two-wire system and optional voltage
range of 1~5V DC can also be available. The transmitter
is supplied factory calibrated, but also has zero and span
potentiometers for field adjustment or calibration.
T75X provides a loop powered 4~20mA/2-wire with LED
local display and in the harzadous environment,
explosion protected terminal head can be also available.
Current output Voltage output
Electrical connection type 2-wire technique 3 or 4-wire technique
Full scale output signal 20mA ±0.2% 5V ±0.2%
Zero measured output 4mA ±0.03% 1V ±0.03%
Other output signals available on request
Excitation voltage 12~36V DC
Load resistance max@24V 500Ω at 24V
Influence of excitation 0.01% FSO/V
Shock resistance No change in performance after 10Gs for 11ms
Vibration 5 g (10…2000Hz)
Response time(10~90%) ±2 milliseconds
Adjustment range ±20% FSO/zero and span
Accuracy ±0.25% FSO
Non-linearity Better than 0.10% FSO
Repeatability Better than 0.05% FSO
Long term stability Better than 0.05% FSO per month
Cutoff frequency(-3 d B) ±2kHz
Ambient temperature limits -20~70°C
Ambient humidity limits 5 to 99% R.H
Process connection PT1/2″male thread
Flange & other connections available on request
Process media Gases and liquids compatible with stainless steel 316
Materials wetted by process Stainless steel 316L and others available on request
Material of terminal head Aluminum die-casting
Local display range LED 31/2 digit
Enclosure rating IP65
Explosion protection Ex d IIC T6
Influence of mounting position Not critical
Options Protection well
Note