SCONI-1500多積積分MULTI INTEGRATING TOTALIZER
Features
It is able to 10 digit total integration and 4 digit rate
display..
It can be accepts multi input signal such as pulse,
mA, Volt signal.
It is improved reliability by use of high resolution
V/F converter.
It contains various batch function which can be use
of various purposes.
It is able to RS 422/485 communication function
which can be use of remote control and
monitoring .
It can be install 2 alarm point which can be set up
rate alarm, batch function and dead band.
It can be install isolated current, voltage output and
also possible output scaling.
It has pulse output function which can be outputs
external integrating total.
SCONI - 1 500 - □ □ - □
Input signal
Output signal (1)
Output signal (2)
Power supply
Name of each part
Type Range Value Display
DC 4 ~ 20mA mA / Volt
DC 1~5V
0 ~ 9999 RNG0
Pulse 1 0.1 ~ 10Hz 0 ~ 9999 RNG1
Pulse 2 1 ~ 100Hz 0 ~ 9999 RNG2
Pulse 3 10 ~ 1KHz 0 ~ 9999 RNG3
1 2 Alarm (SPST)
R Other
N Not used
1 DC 1 ~ 5V
2 DC 4 ~ 20mA
3 RS - 422 / 485
R Other
N Not used
Features
It is able to 10 digit total integration and 4 digit rate
display..
It can be accepts multi input signal such as pulse,
mA, Volt signal.
It is improved reliability by use of high resolution
V/F converter.
It contains various batch function which can be use
of various purposes.
It is able to RS 422/485 communication function
which can be use of remote control and
monitoring .
It can be install 2 alarm point which can be set up
rate alarm, batch function and dead band.
It can be install isolated current, voltage output and
also possible output scaling.
It has pulse output function which can be outputs
external integrating total.
X AC 110V / 220V
Y DC 24V
mA , Volt
Multi
Pulse
① Total count display
② Rate value display
③ Pulse output display
④ Alarm status display
⑤ Total count / Reset count display
⑥ ⑦ ⑧ ⑨ : Set up data and change key
General Specification
Terminal connection
Main functions
Rate scaling function
- In case of input is mA/Volt : This function changes
and set up rate value as scale and input range
change.
- In case of input is pulse : This function converts input
pulse count into rate value which calculates count
factor and Rate time unit.
Function
LIN It transfers input value into output without any
operation. It is used to input process which
requires linearity and general measurement.
Root It transfers input by square root and used to
measure flow with orifice.
Limit This function displays zero when does not
need under display such as level
measurement.
Integration function
- In case of input is current and voltage(mA, Volt) :
It integrates rate value by compensation of time unit
and integration rate.
- In case of input is pulse : It integrates input pulse by
dividing total unit per pulse(count factor).
Alarm mode and batch function
- Rate Alarm(2 Point) : There are 2 alarm point which
can be set up upper and lower limit respectively. And
also outputs relay contact output in compare with
rate value.
- Count Alarm + Rate Alarm : Alarm 1 is an over
alarm for reset count value and alarm 2 is an alarm
for rate value. Alarm 2 operates exactly same as
rate alarm. Alarm 1 operates when reset count value
over set up value.
- 2 Count Alarm : Alarm 1,2 are over alarms for reset
count value and operates when reset count value
over set up value. Alarm is reseted when resets
reset count.
- Batch (Dosage) : It is possible sequential process
with this function when fills a vessel with a fixed rate.
It can be control of flow when approachs target value
by 2 output contacts for precision control.
Communication function
It can be install communication function which can be use
of remote control in connection with computer.
Item Specification
Input
Resistance
Volt(mA) Input : 250Ω
Pulse Input : 10㏀
Measure/Display
Period
Rate value : 200ms(Volt, mA, Input)
Total count : 1s(Volt, mA, Input)
(Pulse input depends on frequency)
CMRR More than 140dB
NMRR More than 60dB
Filter Transfer average filter
Sensor Power DC 12V/30㎃/±0.5%
Rate
Linearity : 0.05% FS
Repeatability : 0.1% FS
Temperature Drift : 0.02% FS/℃
Long term drift : 0.1%/per 1000hr
Totalize
Function
Data Storage : More than 10yrs
Max Count : 10 Digit
Pulse Output
Output type : Isolated open collector
Rating : Max DC 50V/50mA
Max freq : Less than 5Hz
Communication RS - 422/485 (4800 bps)
Relay Contact AC 125V(2A) , DC 30V(3A)
4~20mA DC(0 ~ Load 600Ω)
Resistance 0~10V DC(1㏀ or more)
Isolation Input/Output, DC 500V
More than 100㏁
Dielectric
Strength Input/Output/Power, AC 1500V/ min
AC 110/220V ±10%(50/60Hz) 4VA
Power Supply
DC 24V ±10%, Less than 100mA
Operating Temp -10 ~ 60℃
Operating
Humidity 10 ~ 90%
Weight Approx 500gr(AC), 300gr(DC)
Material/Color ABS Resin / Black
Dimension W 96 x H 48 x D 112 (mm)
Mounting Panel Flush
1 2 3 4 5 6 7
11 12 13 14 15 16 17
8 9 10
OUTPUT2 RS485
(Open. C)
+
DC 20-30V*
FG AC 110V
+ AC 220V
POWER SOURCE
-
18 19 20
+ - + + - + -
PULSE 통신
V, mAPulse RESET
O.C 1㏀
IN1 IN2 DC 12V
OUTPUT1 AL 1 AL 2
(AO)