SCP-51B SCP-52B SCP-53B電路保護器Circuit Protectors
Type : SCP-B Type
▷ Bolt on Type(SCP-B)
- 0.1 ~ 100A: Max. AC380V (3 pole), AC250V (1, 2 pole), DC 80V
- 1 ~ 3 pole, UL 1077 listed, CSA, VDE-064
- Hydraulic / Magnetic Circuit Breaker
- Breaking Capacity: 1.5 kA, AC250V
Ampere Frame | 100 | ||||
Type | SCP-51B | SCP-52B | SCP-53B | ||
Rating | Pole | 1 | 2 | 3 | |
Rated Current(ln) | 1 ,2, 3, 5, 7, 10, 15, 20, 25, 30, 34, 40, 45, 50, 60, 75, 100 | ||||
Rated Operating Voltage(Ue) | AC(V) | 220 | 380 | ||
DC(V) | 80 | ||||
Operating Characteristics | Instantaneous(I), High(H), Middle(M), Low(L) | ||||
Rated Breaking Capacity(kA)(Sym) | AC 250V | 1.5kA (2kA) | |||
KSC8321, IEC60934, UL1077 | DC 80V | 5kA | |||
Number of Operating Cycles | Without Current | 35,000 | |||
With Current | 10,000 | ||||
Dimension (mm) | a | 19 | 38 | 57 | |
b | 63.5 | ||||
c | 47 | ||||
d | 21 | ||||
Weight (kg) | 0.1 | 0.2 | 0.3 | ||
Overcurrent Tripping method | Hydraulic-Magnetic method(HM) | ||||
Connection | BOLT | ||||
Internal Circuit | Series Trip | S | O | ||
Parallel Trip | P | O | |||
Switch only | O | O | |||
Relay Trip | R | O | |||
Accessories | Aux. Switch | W | O | ||
Alarm Switch | A | O | |||
Voltage Trip | C | O | |||
Aux. Contact Capacity | AC 250V 3A, DC 65V 3A |