工頻耐壓試驗(yàn)裝置是發(fā)電站、供配電系統(tǒng)及科研單位等廣大用戶的基本試驗(yàn)設(shè)備。用于對各種電器產(chǎn)品、電氣設(shè)備、絕緣材料等進(jìn)行規(guī)定電壓下的絕緣強(qiáng)度試驗(yàn),考核產(chǎn)品的絕緣水平,發(fā)現(xiàn)被試品的絕緣缺陷,衡量承受過電壓的能力。
輸入電壓:AC 220(380)V 可選
低壓輸出:AC 0-250(430)V
低壓電流:0-5/10/15/50A(可按客戶要求定制)
輸出容量:0-3/5/10/15 kVA(可按客戶要求定制)
高壓電壓:0-50/100/150/200 kV(可按客戶要求定制)
高壓電流:0-50/100/150/200/500/1000/2000mA(可按客戶要求定制)
計(jì)時(shí)范圍:0-9999S
環(huán)境溫度:-20℃至50℃
電壓精度:≤1.5% ±1個(gè)字(F.S)
電流精度:≤1.5% ±1個(gè)字(F.S)
控制箱參數(shù):
型號規(guī)格 | 容量 | 輸入電源 | 輸出電壓 | 重量(kg) | |||
KVA | 相數(shù) | (V) | (A) | (V) | (A) | ||
BOT-1200-2/220 | 2 | LN | 220 | 10 | 0-250 | 8 | 14 |
BOT-1200-3/220 | 3 | LN | 220 | 15 | 0-250 | 12 | 16 |
BOT-1200-5/220 | 5 | LN | 220 | 25 | 0-250 | 20 | 18 |
BOT-1200-10/220 | 10 | LN | 220 | 50 | 0-250 | 40 | 80 |
BOT-1200-15/400 | 15 | AB | 380 | 37.5 | 0-430 | 34.8 | 90 |
BOT-1200-20/400 | 20 | ABN | 380 | 50 | 0-430 | 46.5 | 100 |
BOT-1200-25/400 | 25 | ABN | 380 | 62.5 | 0-430 | 58.1 | 120 |
BOT-1200-30/400 | 30 | ABN | 380 | 75 | 0-430 | 69.7 | 140 |
BOT-1200-50/400 | 50 | ABN | 380 | 125 | 0-430 | 116.2 | 160 |
BOT-1200-100/400 | 100 | ABN | 380 | 250 | 0-430 | 232.5 | 250 |
說明: 1、如有特殊參數(shù)要求,可按用戶的技術(shù)參數(shù)進(jìn)行設(shè)計(jì)制作。 2、輸出容量為5kVA以下(含5KVA)時(shí)控制部分為箱式,其它都為臺式。 |
高壓電壓輸出顯示精度:FS×1.5%±2個(gè)字
高壓電流輸出顯示精度:FS×2.0%±2個(gè)字
低壓電流輸出顯示精度:FS×1.5%±2個(gè)字
試驗(yàn)變壓器參數(shù):
規(guī)格 | 容量 | 低壓側(cè) | 高壓側(cè) | 高壓側(cè)(交直流變壓器) | 測量變比 | 30分鐘溫升 | 阻抗電壓 | 空載電流 | 重量 | |||
電壓 | 電流 | 交流輸出 | 直流輸出 | |||||||||
KVA | V | A | 電壓KV | 電流 | 電壓KV | 電流 | ℃ | % | % | kg | ||
1.5/50 | 1.5 | 200 | 7.5 | 50 | 30 | 70 | 21.4 | 500 | 10 | 10 | <> | 19.5 |
3/50 | 3 | 200 | 15 | 50 | 60 | 70 | 42.9 | 500 | 10 | 10 | <> | 27 |
5/50 | 5 | 200 | 25 | 50 | 100 | 70 | 71.4 | 500 | 10 | 10 | <> | 52 |
10/50 | 10 | 200 | 50 | 50 | 200 | 70 | 142.9 | 500 | 10 | 10 | <> | 80 |
15/50 | 15 | 400 | 37.5 | 50 | 300 | 70 | 214.3 | 500 | 10 | 8 | <> | 120 |
20/50 | 20 | 400 | 50 | 50 | 400 | 70 | 285.7 | 500 | 10 | 8 | <> | 140 |
30/50 | 30 | 400 | 75 | 50 | 600 | 70 | 428.6 | 500 | 10 | 8 | <> | 155 |
50/50 | 50 | 400 | 125 | 50 | 1000 | 70 | 714.3 | 500 | 10 | 8 | <> | 184 |
10/100 | 10 | 200 | 50 | 100 | 100 | 140 | 71.4 | 1000 | 10 | 10 | <> | 135 |
15/100 | 15 | 400 | 37.5 | 100 | 150 | 140 | 107.1 | 1000 | 10 | 8 | <> | 150 |
20/100 | 20 | 400 | 50 | 100 | 200 | 140 | 142.9 | 1000 | 10 | 8 | <> | 215 |
30/100 | 30 | 400 | 75 | 100 | 300 | 140 | 214.3 | 1000 | 10 | 8 | <> | 250 |
50/100 | 50 | 400 | 125 | 100 | 500 | 140 | 357.1 | 1000 | 10 | 8 | <> | 290 |
10/150 | 10 | 200 | 50 | 100 | 66.7 | 140 | 47.6 | 1500 | 10 | 10 | <> | 180 |
15/150 | 15 | 400 | 37.5 | 150 | 100 | 210 | 71.4 | 1500 | 10 | 8 | <> | 200 |
20/150 | 30 | 400 | 50 | 150 | 133.3 | 210 | 95.2 | 1500 | 10 | 8 | <> | 220 |
30/150 | 30 | 400 | 75 | 150 | 200 | 210 | 142.9 | 1500 | 10 | 8 | <> | 280 |
50/150 | 50 | 400 | 125 | 150 | 333.3 | 210 | 238.1 | 1500 | 10 | 8 | <> | 340 |
說明: 1、如有特殊參數(shù)要求,可按用戶的技術(shù)參數(shù)進(jìn)行設(shè)計(jì)制作。 2、上表的重量以油浸式試驗(yàn)變壓器為例,干式試驗(yàn)變壓器和充氣式試驗(yàn)變壓器稍有不同。 |