| |  | | Built in Microprocessor |  | | Selectable alarm circuit max. 64 CH |  | | 4 function Sequence (default : Inspection Sequence) |  | | Bell or Buzzer selectable by DIP switches on every channel | | | Automatic or manual alarm stop |  | | LED lamp with various color |  | | selectable NO/NC input | | |
|
|
| |  | | | | | | |  | | ???? ? ???? | | | | | | | | | |
|
|
| | Rating voltage | DC 24V | Power consumption | YS ANS 8 | About 10W | YS ANS 15 | About 12W | YS ANS 16 | About 13W | YS ANS 21 | About 20W | YS ANS 32 | About 30W | YS ANS 64 | About 60W | Fault signal | Type | NO/NC | Duration time | Above 15msec | Field contact voltage | DC 24V, 48V, 110V, 220V (Fixed at factory) | Lamp rating | DC 24V 20mA | Lamp color | Red, Green, Yellow, Orange, Blue, White | Ambient temperature | -25~40℃ | Relative humidity | 45~85% | | |
|
|
| |  | | This annunciator is a intergrated display system and a concentrated alarm equipment to display and to alarm | | | a trouble of equipment and operating status. It is miniatured and well treated unit which used microprocessor. It is designed to make more function change and maintenance than a rack type because it is adapted to card inserting method using solid state type. | | |
|
|
| |  | | The ANS can select BELL and BUZZER by dip switch. It can be tested by lamp test button. Being the | | | fault signal in each channel, The ANS sends alarm output toward bell or buzzer and then send flicker output to the display unit that correspond to each channel. After checking the alarm, if is selected auto alarm stop, the alarm is canceled passing 15 sec. but indication LED keeps being lighted. Reset after eliminating all fault signal sources. 1) You can select bell or buzzer according to light or heavy fault at each channel. It is located in bottom side. We will recommand that the red LED correspond to BELL. 2) Connect the line according to a connection diagram then check LED lamp through lamp test button. 3) Check the sequence what user selected through operation test button. 4) Lamp is out off normal operating and if the abnormal signal appears, a corresponding lamp starts to flicking. | | |
|
|
| |  | | The lamp is LED type which divided into 6 color(Red, Green, Yellow, Orenge, Blue, White). | | | So, customer can choose various color of lamp and use what color they want. Each unit can be writed product name and No. on the body. The size of lamp is 30×40mm. (Please order of what LED color.) | | |
|
|
|
|
|
| |  | | BASIC SEQUENCE | | | Generally, It is used to a alarm system. When the abnormal signal is occured, a LED lamp starts on flicking and alarm for the operator. When push acknowledge button, lamp and alarm is stopped and return to normal operating stage. | | |
|
| |  | | BASIC SEQUENCE | | | This alarm system is the same as basic sequence for an operating function with memorizing function of input alarm signal. In case of using of this system, even fault signal contact resource is returned to normal state, it is to be indicated lighting. If the operator push acknowledge button, an alarm is stopped and lamp is transferred from flicking to normal lamp. If reset button is pushed, lamp is out off and to be returned to normal operating state. This system is only typical for lock in type. | | |
|
| |  | | RING BACK SEQUENCE | | | This alarm system of operating is the same as a basic sequence but lamp is fast flashing at alarm sounding. At this time, pushed acknowledge button, lamp is changed to slow flashing and sound is also changed to buzzer. If reset button is pushed, alarm sound is off and returned to normal state. This alarm system is a sequence used in case that we know abnormal state is dissolved at the non rock input and a system for informing that alarm state is restored to normal state. | | |
|
| |  | | FIRST OUT SEQUENCE | | | This alarm system is the sequence that distinguished between the first abnormal signal and subsequent signal. Alarm lamp of abnormal signal that appears first is fast flicking and alarm sound rings and that of abnormal signals that appears after that is slow flicking. At this time, if acknowledge button is pushed, alarm sound is stopped. Alarm lamp which is fast flicking is slow flicking, and other alarm lamps keep lighting state, but they are off when abnormal signal is cleared. At this time, if reset button is pushed, get normal state. However, after acknowledge button is pushed and before reset button is pushed if abnormal signal appears, alarm lamp is slow flicking. | | |
|
|
|