Supply voltage | | |
Rated value (DC) | | |
| Yes | Yes |
Input current | | |
Current consumption, typ. | 45 mA | 45 mA |
from backplane bus 5 V DC, typ. | 80 mA | 80 mA |
Power loss | | |
Power loss, typ. | 1.5 W | 1.5 W |
Analog outputs | | |
Number of analog outputs | 2; Current or voltage | 4; Current or voltage |
Output ranges, voltage | | |
| Yes | Yes |
Output ranges, current | | |
| Yes | Yes |
Load impedance (in rated range of output) | | |
| 1 000 ? | 1 000 ? |
| 600 ? | 600 ? |
Analog value generation for the outputs | | |
Integration and conversion time/resolution per channel | | |
| Voltage: 14 bits; Current : 13 bits | Voltage: 14 bits; Current : 13 bits |
Errors/accuracies | | |
Temperature error (relative to output range), (+/-) | 25 °C ±0.3%, to 55 °C ±0.6% total measurement range | 25 °C ±0.3%, to 55 °C ±0.6% total measurement range |
Basic error limit (operational limit at 25 °C) | | |
| 0.3 % | 0.3 % |
| 0.3 % | 0.3 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | | |
| 12 V | 12 V |
Interrupts/diagnostics/status information | | |
Alarms | Yes | Yes |
Diagnostic functions | Yes | Yes |
Alarms | | |
| Yes | Yes |
Diagnostic messages | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Diagnostics indication LED | | |
| Yes | Yes |
| Yes | Yes |
Degree and class of protection | | |
Degree of protection acc. to EN 60529 | | |
| Yes | Yes |
Standards, approvals, certificates | | |
CE mark | Yes | Yes |
CSA approval | Yes | Yes |
FM approval | Yes | Yes |
RCM (formerly C-TICK) | Yes | Yes |
Ambient conditions | | |
Free fall | | |
| 0.3 m; five times, in product package | 0.3 m; five times, in product package |
Ambient temperature during operation | | |
| -20 °C | -20 °C |
| 60 °C | 60 °C |
| -20 °C | -20 °C |
| 60 °C | 60 °C |
| -20 °C | -20 °C |
| 50 °C | 50 °C |
Ambient temperature during storage/transportation | | |
| -40 °C | -40 °C |
| 70 °C | 70 °C |
Air pressure acc. to IEC 60068-2-13 | | |
| 795 hPa | 795 hPa |
| 1 080 hPa | 1 080 hPa |
| 660 hPa | 660 hPa |
| 1 080 hPa | 1 080 hPa |
Relative humidity | | |
| 95 % | 95 % |
Pollutant concentrations | | |
| S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
Connection method | | |
required front connector | Yes | Yes |
Mechanics/material | | |
Enclosure material (front) | | |
| Yes | Yes |
Dimensions | | |
Width | 45 mm | 45 mm |
Height | 100 mm | 100 mm |
Depth | 75 mm | 75 mm |
Weights | | |
Weight, approx. | 180 g | 180 g |