Product description | |
Model | Suffix code | Description | ED6 | □ | □ | □ | □ | □ | Aspect 77 x 35 mm | Control Operation | F | - | - | - | | ON/OFF Operation | P | | | | | Proportional Operation (P control) | Input Sensor | K | - | - | | K(CA) | • Range : -80.0 ~ 999.9 °C |
| P | - | - | | Pt100(Din) | • Range : -100.0 ~ 400.0 °C |
| C | | | | 1 ~ 5 V DC | • Range : -1000 ~ 5000 | 4 ~ 20 mA DC | (* attach 250 Ω (± 0.1 %) resistor in input terminal) |
| Output Control | M | - | | Relay Contact Point | S | | | SSR Output (Voltage Pulse 5 V DC) | Options | A | | Alarm & Defrost | N | | None | Power Supply | P3 | 10 ~ 24 V DC, AC | P4 | 100 ~ 240 V AC |
Power Supply | Refer to “Power Supply” in “Model and Suffix Code” | Power Consumption | Below 5 VA | Input Sensor | Refer to “Input Sensor” in “Model and Suffix Code” | Display Accuracy | Max range (FS ± 0.5 % +1 Digit) | Output Control (Main Output) | Relay Output | 250 V AC 5 A (resistive load) | SSR Output | 5 V DC 50 mA (max) |
| Alarm & Defrost | Relay Output | 250 V AC 5 A (resistive load) |
| Control Operation | Two Position Operation (ON/OFF) | Proportional Operation (P) |
| Setting Method | Digital method by setting, up and down keys | Other Functions | Auxiliary output(Alarm & Defrosting Timer) | Heating/cooling |
| Resistance between wires | Thermocouple type (CA) | Below 100 Ω for each wire | Resistive type (Pt 100 Ω) | Below 10 Ω for each wire (Resistance of 3 wires should be the same.) |
| Operating Ambient Temperature/Humidity | 0 ~ 50 ˚C / below 35 ~ 85 % R.H (no condensation) |
| | |